Noise data cooling only, Blucube ™ condensing unit, Condensing units – Airedale BluCube 10-48kW User Manual

Page 46

Advertising
background image





BluCube

Condensing Unit

46

Condensing Units

Technical Manual : 7206188 V1.6.0_07 2014

Noise Data Cooling Only

Sound

Frequency (Hz)

Measurement

dBa

63

125

250

500

1000

2000

4000

8000

CUR092V16-1CO-0

Power

dB

86.4

81.2

84.9

79.5

84.6

83.9

73.6

63.4

57.1

Pressure

@ 1m

78.4

73.2

76.9

71.5

76.6

75.9

65.6

55.4

49.1

Pressure

@ 10m

58.4

53.2

56.9

51.5

56.6

55.9

45.6

35.4

29.1

CUR092V20-1CO-0

Power

dB

86.6

81.5

84.9

79.5

84.6

84.1

74.2

64.4

57.9

Pressure

@ 1m

78.6

73.5

76.9

71.5

76.6

76.1

66.2

56.4

49.9

Pressure

@ 10m

58.6

53.5

56.9

51.5

56.6

56.1

46.2

36.4

29.9

CUR092V25-1CO-0

Power

dB

86.6

81.0

85.0

79.5

84.6

84.1

73.9

64.4

58.3

Pressure

@ 1m

78.6

73.0

77.0

71.5

76.6

76.1

65.9

56.4

50.3

Pressure

@ 10m

58.6

53.0

57.0

51.5

56.6

56.1

45.9

36.4

30.3

CUR092V29-1CO-0

Power

dB

86.6

81.5

84.9

79.5

84.6

84.1

74.2

64.4

57.9

Pressure

@ 1m

78.6

73.5

76.9

71.5

76.6

76.1

66.2

56.4

49.9

Pressure

@ 10m

58.6

53.5

56.9

51.5

56.6

56.1

46.2

36.4

29.9

CUR122V35-1CO-0

Power

dB

86.9

96.5

95.4

87.2

85.0

80.5

75.2

68.3

68.2

Pressure

@ 1m

78.9

88.5

87.4

79.2

77.0

72.5

67.2

60.3

60.2

Pressure

@ 10m

58.9

68.5

67.4

59.2

57.0

52.5

47.2

40.3

40.2

CUR122V40-1CO-0

Power

dB

87.3

96.5

95.4

87.3

85.0

81.4

76.3

69.5

68.5

Pressure

@ 1m

79.3

88.5

87.4

79.3

77.0

73.4

68.3

61.5

60.5

Pressure

@ 10m

59.3

68.5

67.4

59.3

57.0

53.4

48.3

41.5

40.5

CUR092V16-VCO-0

Power

dB

86.7

80.9

84.9

79.6

84.8

84.2

73.4

64.4

60.8

Pressure

@ 1m

78.7

72.9

76.9

71.6

76.8

76.2

65.4

56.4

52.8

Pressure

@ 10m

58.7

52.9

56.9

51.6

56.8

56.2

45.4

36.4

32.8

CUR092V20-VCO-0

Power

dB

86.7

80.9

84.9

79.6

84.9

84.2

73.7

66.1

59.8

Pressure

@ 1m

78.7

72.9

76.9

71.6

76.9

76.2

65.7

58.1

51.8

Pressure

@ 10m

58.7

52.9

56.9

51.6

56.9

56.2

45.7

38.1

31.8

CUR092V25-VCO-0

Power

dB

87.0

80.9

84.9

79.8

85.4

84.1

74.9

67.1

60.2

Pressure

@ 1m

79.0

72.9

76.9

71.8

77.4

76.1

66.9

59.1

52.2

Pressure

@ 10m

59.0

52.9

56.9

51.8

57.4

56.1

46.9

39.1

32.2

CUR092V29-VCO-0

Power

dB

87.0

80.9

84.9

79.7

85.5

84.3

74.6

66.4

59.9

Pressure

@ 1m

79.0

72.9

76.9

71.7

77.5

76.3

66.6

58.4

51.9

Pressure

@ 10m

59.0

52.9

56.9

51.7

57.5

56.3

46.6

38.4

31.9

CUR122V35-VCO-0

Power

dB

87.5

96.4

95.4

87.3

85.8

81.2

76.5

70.5

68.8

Pressure

@ 1m

79.5

88.4

87.4

79.3

77.8

73.2

68.5

62.5

60.8

Pressure

@ 10m

59.5

68.4

67.4

59.3

57.8

53.2

48.5

42.5

40.8

CUR122V40-VCO-0

Power

dB

87.6

96.4

95.4

87.3

85.7

81.4

77.2

70.9

69.0

Pressure

@ 1m

79.6

88.4

87.4

79.3

77.7

73.4

69.2

62.9

61.0

Pressure

@ 10m

59.6

68.4

67.4

59.3

57.7

53.4

49.2

42.9

41.0


*sound data is for AC fan at full speed and modulating compressor at 100%
**sound pressure calculated using hemi-spherical propogation

Notes:

1

Sound Power Reference Power = 10-12 Watts.

2

Sound Pressure Reference Pressure = 2 x 10-5 N/m2.

3

dBA is the overall noise level, measured on the A scale.

4

Sound Pressure data is only valid in free field conditions, where a reflective surface, such as a roof is found.