Interconnecting wiring, Heat pump, Condensing units blucube – Airedale BluCube 10-48kW User Manual

Page 61

Advertising
background image







Condensing Units

BluCube

Condensing Units

61

Technical Manual : 7206188 V1.6.0_07_2014

Interconnecting Wiring

– Heat Pump

B

luCu

b

e

L1

Mains incoming supply 400V/3PH/50Hz

L2

L3

N

PE

502

24 Volts AC

551

Cooling Signal

552

Heating Signal

500

0 Volts

845

Variable Capacity Compressor Only

0-10Volts Compressor demand

500

0 Volts

567

Defrost Status Normally Open

568

Defrost Status Normally Closed

569

Common

561

NO

Critical alarm Normally Open

562

Common

GND

563

NC

Critical alarm Normally Closed


Rx-Tx-

Use Awg20/22 twisted pair (with overall shield) cable,
Belden ref. 8762 (Airedale ref: 6110316), or equivalent,
for

network

Network Connections (Inward connection)

Rx+Tx+

GND

Rx-Tx-

Use Awg20/22 twisted pair (with overall shield) cable,
Belden ref. 8762 (Airedale ref: 6110316), or equivalent,
for

network

Network Connections (Outward connection)

Rx+Tx+

GND



pLAN Termination