Interconnecting wiring, Condensing units blucube – Airedale BluCube 10-48kW User Manual

Page 45

Advertising
background image







Condensing Units

BluCube

Condensing Units

45

Technical Manual : 7206188 V1.6.0_07_2014

Interconnecting Wiring

Blu

C

u

b

e

L1

Mains incoming supply 400V/3PH/50Hz

L2

L3

N

PE

502

24 Volts AC

551

Cooling Signal

845

Variable Capacity Compressor Only

0-10Volts Compressor demand

800

0 Volts

561

NO

Critical alarm Normally Open

562

Common

GND

563

NC

Critical alarm Normally Closed


Rx-Tx-

Use Awg20/22 twisted pair (with overall shield) cable,
Belden ref. 8762 (Airedale ref: 6110316), or equivalent,
for

network

Network Connections

(Inward connection)

Rx+Tx+

GND

Rx-Tx-

Use Awg20/22 twisted pair (with overall shield) cable,
Belden ref. 8762 (Airedale ref: 6110316), or equivalent,
for

network

Network Connections

(Outward connection)

Rx+Tx+

GND

pLAN Termination

Advertising