Blucube ™ condensing unit, Condensing units – Airedale BluCube 10-48kW User Manual

Page 54

Advertising
background image





BluCube

Condensing Unit

54

Condensing Units

Technical Manual : 7206188 V1.6.0_07 2014

Mechanical Data - Heat Pump Fixed Capacities Continued

CUR092V29-1HP-0

CUR122V35-1HP-0

CUR122V40-1HP-0

Capacity

Nominal Cooling Capacity

(1)

kW

28.7

39.7

44.1

Nominal Heating Capacity

(2)

kW

26.4

35.5

39.2

Capacity Steps

1

1

1

Dimensions

– W x D x H

(3)

mm

922 x 764 x 1736

1222 x 764 x 1736

1222 x 764 x 1736

Masses

– Machine / Operating

(4)

kg

262

316

324

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint

– Light Grey (RAL 7035)

Material/Colour

Heat Pump Evaporator / Condenser

Rifled Copper Tube/Louvered Hydrophilic Coated Aluminium Fins

Fan Motor

Axial

Motor Type

AC 1ph

AC 3ph

AC 3ph

Quantity x Motor Size

kW

1 x 0.6

1 x 1.97

1 x 1.97

Diameter

mm

630

630

630

Maximum Fan Speed

RPM

895

1330

1330

Maximum Airflow

m³/s

2.0

3.5

3.5

Compressor

Compressor Type

Fixed Capacity Scroll

Quantity

1

1

1

Oil Charge Volume

l

3.3

3.3

3.6

Oil Type

Polyolester

Refrigeration

Single Circuit - 2 pipe configuration

Refrigerant control and type

Optional REEV package

Refrigerant type

R410A

Holding Charge

Inert Gas

Coil Volume

l

18.67

21.65

21.65

Refrigerant Charge

(5)

kg

6.82

7.15

7.15

Connections

Liquid (sweat)

in

1/2

1/2

5/8

Suction / Discharge (sweat)

in

7/8

7/8

1 1/8

Optional Extras

EC Fan

Quantity x Motor Size

kW

1 x 0.72

1 x 1.85

1 x 1.85

Diameter

mm

630

630

630

Maximum Fan Speed

RPM

1000

1230

1230

Maximum Airflow

m³/s

2.3

3.5

3.5

Dimensions

– W x D x H

(2)

mm

922 x 764 x 1750

1222 x 764 x 1750

1222 x 764 x 1750

Masses

– Machine / Operating

(3)

kg

254

308

316

Short Case Axial Fan

Designed to 75Pa ESP

Quantity x Motor Size

kW

1 x 1.4

N/A

N/A

Diameter

mm

560

N/A

N/A

Maximum Fan Speed

RPM

1330

N/A

N/A

Maximum Airflow

m³/s

2.8

N/A

N/A

Dimensions

– W x D x H

(2)

mm

922 x 764 x 1753

N/A

N/A

Masses

– Machine / Operating

(3)

kg

268

N/A

N/A

REEV Selection

E²V - 35

E²V - 45

E²V

– 45

(1) Evaporating temperature 7°C, Ambient 35°C with an AC fan matched with a REEV package
All performance data is supplied in accordance with BS EN 14511-1:2013
(2) Condensing temperature 50°C, Ambient 5°C with an AC fan matched with a REEV package
(3) Overall dimensions for clearance

(4) Unit mass excludes a refrigerant charge

(5) For guidance only

Advertising