Condensing units blucube, Condensing units – Airedale BluCube 10-48kW User Manual

Page 33

Advertising
background image







Condensing Units

BluCube

Condensing Units

33

Technical Manual : 7206188 V1.6.0_07_2014

Refrigeration Pipe Sizing Guide
Cooling Only

Equivalent Pipe Lengths with R410A

Outdoor

Unit

0-20m

Suction

20-40m

Suction

40-60m

Suction

60-80m

Suction

Connection Size

Liquid

Suction

Liquid

H

V

Liquid

H

V

Liquid

H

V

Liquid

H

V

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

CUR092V16-1CO-0

3/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

CUR092V20-1CO-0

1/2

1 1/8

1/2

1 3/8

7/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V25-1CO-0

1/2

1 3/8

1/2

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V29-1CO-0

1/2

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

CUR122V35-1CO-0

5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

CUR122V40-1CO-0

5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

CUR092V16-VCO-0

3/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

CUR092V20-VCO-0

1/2

1 1/8

1/2

1 3/8

1 1/8

1/2

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V25-VCO-0

1/2

1 3/8

1/2

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V29-VCO-0

1/2

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

CUR122V35-VCO-0

5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

CUR122V40-VCO-0

5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

7/8

1 5/8

1 5/8

Heat Pump

Equivalent Pipe Lengths with R410A

Outdoor

Unit

Connection Size

0-20m

Suction / Disch

20-40m

Suction / Disch

40-60m

Suction / Disch

60-80m

Suction / Disch

Liquid

Suction

Disch

Liquid

H

V

Liquid

H

V

Liquid

H

V

Liquid

H

V

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

CUR092V16-1HP-0

3/8

1/2

1/2

3/4

1/2

1/2

3/4

5/8

1/2

3/4

5/8

1/2

3/4

5/8

CUR092V20-1HP-0

3/8

5/8

1/2

7/8

5/8

5/8

7/8

5/8

5/8

7/8

5/8

5/8

7/8

5/8

CUR092V25-1HP-0

1/2

7/8

1/2

1 1/8

5/8

5/8

1 1/8

3/4

5/8

1 1/8

3/4

5/8

1 1/8

3/4

CUR092V29-1HP-0

1/2

7/8

5/8

1 1/8

3/4

5/8

1 1/8

3/4

3/4

1 1/8

3/4

3/4

1 1/8

3/4

CUR122V35-1HP-0

1/2

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

CUR122V40-1HP-0

5/8

1 1/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

CUR092V16-VHP-0

3/8

1/2

1/2

7/8

1/2

1/2

7/8

1/2

1/2

7/8

1/2

1/2

7/8

1/2

CUR092V20-VHP-0

3/8

5/8

1/2

7/8

5/8

1/2

7/8

5/8

5/8

7/8

5/8

5/8

7/8

5/8

CUR092V25-VHP-0

1/2

7/8

1/2

1 1/8

5/8

5/8

1 1/8

5/8

5/8

1 1/8

5/8

5/8

1 1/8

5/8

CUR092V29-VHP-0

1/2

7/8

5/8

1 1/8

3/4

5/8

1 1/8

3/4

5/8

1 1/8

3/4

5/8

1 1/8

3/4

CUR122V35-VHP-0

1/2

7/8

3/4

1 3/8

3/4

3/4

1 3/8

3/4

3/4

1 3/8

3/4

3/4

1 3/8

3/4

CUR122V40-VHP-0

5/8

1 1/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

7/8

1 3/8

7/8

(1) For interconnecting pipework with a predominantly horizontal layout.

(2) For interconnecting pipework with a predominantly vertical layout.

(3) Careful pipework selection must be done if the liquid line rises. Additional system sub cooling may be required to overcome friction losses.


All pipe sizes have been calculated based on a nominal condition 7°C evaporating and 50°C condensing temperatures.

Suction and discharge double risers may be required during part load operation.

Advertising