Re-orientation to vertical discharge, Orientation to vertical discharge, Installation data – Airedale Air Cooled Condensers R410A User Manual

Page 11

Advertising
background image

Condensers

CR12

– CR105

Condensers

11

Installation & Maintenance : 6680953 V1.2.0 02/2013

Installation Data

RE-ORIENTATION TO VERTICAL DISCHARGE

1

Remove the fixings securing the unit to the pallet.

2

In line with horizontal discharge lifting
instructions, lift the unit sufficiently to gain
access to the lower leg fixings as shown in
Fig 1.





Fig 1

3

Reposition and secure the lower 2 legs to the corner of the unit using the fixings and hole positions provided to both
faces, as Fig 2.


Note, model sizes CR80 & CR105 have an additional mid support leg, this should also be adjusted and
secured.

Fig 2

4

Lower and rest the unit down to floor and reposition and secure the upper legs as described in Step 3.

5

In line with vertical discharge lifting
instructions lift the unit slowly into vertical
orientation as Fig 3.


Fig 3

Care should be taken to ensure the unit does not drop into position and that damage is not sustained
prior to lifting the unit into final position.

6

The unit may be lifted into its final position.