Commissioning Data

CONTROL DEVICE ADJUSTMENT

On-Off Pressure Switch

The control device comprises a pressure switch with on/off contact which cycles
operation of the fan as a function of the pressure; the contact:

Closes and feeds the fan motor when the pressure rises and reaches the
set point (29 barg)

Opens when the pressure falls to a level equal to the set point value, minus the
differential pressure pre-set (23 barg)

This type of control system is suitable where ambient temperatures seldom
fall below

0˚C.

In cold climates it could cause excessive hunting of the system.

The values of Set and Differential are adjusted by means of the adjusting screws which
are accessed by removing the external casing of the pressure switch.

Factory setting: Set

= 26 barg

Differential = 6 barg

OPTIONAL EC FANS

When the condenser is matched to an Airedale indoor unit, head pressure control is
provided by the indoor unit.

The fan speed of unmatched condensers is controlled by the onboard EC fan electronics
connected to a pressure transducer on the outlet manifold.

CAUTION

All fans are supplied pre-programmed to a head pressure setpoint of 26 barg and
proportional band setpoint of 5 barg unless otherwise specified at order.