Installation data, Dimensions / weights / positioning - horizontal, Installation – Airedale Air Cooled Condensers R410A User Manual

Page 8: Data, Condensers, Important, Standard condenser fan (cr12 - cr30 shown), Caution

Advertising
background image

CR12

– CR105

Condensers

8

Condensers

Installation & Maintenance : 6680953 V1.2.0 02/2013

Installation Data

DIMENSIONS / WEIGHTS / POSITIONING - HORIZONTAL

IMPORTANT

The following information is for general guidance; refer to the certified drawings provided
for installation.

The legs attached to the top of the unit are for lifting and stacking and may be removed and
stored safely if not required.

Only 2 units may be stacked together.

Standard Condenser Fan (CR12 - CR30 Shown)





3000

(2)

A

D

B

(5a)

(4)

500

(2)

500

(2)

500

(2)

(1)

(1)

(1)

C

E

(1)

150

150

(5b)

(3)

(6)

(7)

Diagram illustrated in mm

(1)

Airflow

(2)

Minimum clearances

(3)

12.7mm fixing hole

(4)

Mains electric isolator

(5)

Service connections to left hand side of the unit:
a = Discharge gas inlet (ALWAYS above (b))

b = Liquid outlet

(6)

Top brackets may be used to secure unit of similar size
on top, using, 2 x 12.7mm fixing holes

(7)

40mm lifting holes

Optional Short Case Axial Fan (SCAF) (CR80 - CR105 Shown)





3000

(2)

A

D

B

(5b)

(4)

500

(2)

500

(2)

500

(2)

(1)

(1)

(1)

C

E

(1)

150

150

(6)

(3)

D

(1)

(1)

(5a)

(8)

(7)

Diagram illustrated in mm

(1)

Airflow

(2)

Minimum clearances

(3)

12.7mm fixing hole

(4)

Mains electric isolator

(5)

Service connections to left hand side of the unit:
a = Discharge gas inlet (ALWAYS above (b))

b = Liquid outlet

(6)

Top brackets may be used to secure unit of similar size
on top, using, 2 x 12.7mm fixing holes

(7)

40mm lifting holes

(8)

Optional Short Case Axial Fan with integral duct fixing
holes

DIMENSIONS (mm)

WEIGHTS (kg)

Standard Fan

Standard

Fan

Optional

EC Fan

Optional

SCAF

A

B

C

D

E

CR12

907

972

1000

845

700

62

67

67

CR16

907

972

1000

845

700

70

76

75

CR22

1102

1167

1000

1040

700

77

83

88

CR30

1102

1167

1000

1040

700

90

96

101

CR50

2184

1167

1000

2121

700

132

145

154

CR65

2184

1167

1000

2121

700

162

175

184

CR80

3565

1167

1000

1752

700

208

228

242

CR105

3565

1167

1000

1752

700

260

280

294

CAUTION

A vertical air discharge unit is recommended for installation in windy locations or wherever a
horizontal airflow would be obstructed.