Refrigerant charging, Commissioning data – Airedale Air Cooled Condensers R410A User Manual

Page 20

Advertising
background image

CR12

– CR105

Condensers

20

Condensers

Installation & Maintenance : 6680953 V1.2.0 02/2013

Commissioning Data

REFRIGERANT
CHARGING

It is important that the system is charged with the correct amount of refrigerant.
Remember, a seriously over or undercharged system may lead to major
component failure.

The final refrigerant charge level should be set by the design evaporating and condensing
pressures, together with a full or nearly full sight glass.

The suction and discharge pressures should be constantly monitored whilst charging is
in progress.

To calculate the system refrigeration charge, please refer to the indoor unit data.

CR12

CR16

CR22

CR30

Refrigeration

Single Circuit

Refrigerant Type

R410A

Coil Volume

l

3.0

6.0

4.7

9.3

Refrigerant Charge

(1)

kg

1.4

2.7

2.2

4.3

CR50

CR65

CR80

CR105

Refrigeration

Single Circuit

Refrigerant Type

R410A

Coil Volume

l

10.7

21.4

18.3

36.6

Refrigerant Charge

(1)

kg

4.9

9.8

8.4

16.7

(1)

For guidance only.