background image

CUS 15 - 60 / HCU 20 – 30D

Condensing Units

Chiller & Condensing Units

Installation & Maintenance:Part No: 6259592 IM 07\14

12

Dimensions: CUS 40D - 60D

A

C

B

+ A1

+ F1

C1+

D1+

Y

F

Z

G

E

D

SUCTION

LIQUID

6 Fixing Holes Ø 14mm

+

+

F

E

K

J

H

2 Holes Ø 75mm

2 Knockouts Ø 32mm

B1

E1

D

55mm² Lifting Holes

ISOLATOR

ACCESS TO

COMPRESSOR

AIRFLOW

A

B

C

D

E

F

G

H

J

K

CUS 40D

mm

1693

2440

1800

200

1020

75

1650

155

595

100

CUS 50D

mm

1693

2440

1800

200

1020

75

1650

155

595

100

CUS 60D

mm

1693

2440

1800

200

1020

75

1650

155

595

100

Point Loadings (kg)

Centre of Gravity (mm)

A1

B1

C1

D1

E1

F1

Y

Z

CUS 40D

148

174

174

174

174

149

1169

896

CUS 50D

157

206

206

208

206

156

1136

900

CUS 60D

180

254

254

258

255

180

1116

900

Note: Allow 500mm around the unit for airflow and maintenance clearance.