Condensing units, Field connections – Airedale Condensing Units (CU) 3kW - 80kW User Manual

Page 18

Advertising
background image

CUS 15 - 60 / HCU 20 – 30D

Condensing Units

Chiller & Condensing Units

Installation & Maintenance:Part No: 6259592 IM 07\14

18

Field Connections

CUS 15-30

&

HCU 20-30 UNITS

L1

L2

L3

Mains Incoming

N

400/3/50

E

L4

L4-N1 Permanent Supply

N1

230/1/50

500

0V

502

24VAC Customer’s Control

530

502-530 Stage Two Cool - Customer's Control

535

502-535 Stage One Cool - Customer's Control

531

531-500 Liquid Line Solenoid - Circuit 2

Customer
Supply

532

532-500 Liquid Line Solenoid - Circuit 1

526

526-527 Common Volt Free Alarm N/O Contact

527

CUS 40-60 UNITS

L1

L2

L3

Mains Incoming

N

400/3/50

E

L4

L4-N1 Permanent Supply

N1

230/1/50

500

0V

502

24VAC - Customer’s Control

506

502-506 Stage One Cool - Customer's Control

513

502-513 Stage Two Cool - Customer's Control

522

522-552 Stage Three Cool - Customer's Control

552

523

523-555 Stage Four Cool - Customer's Control

555

507

507-500 Liquid Line Solenoid 1 - Circuit 1

Customer
Supply

514

514-500 Liquid Line Solenoid 2 - Circuit 2

507

507-500 Liquid Line Solenoid 1 - Comp 1, Circuit 1

514

514-500 Liquid Line Solenoid 2 - Comp 1, Circuit 2

522

522-500 Liquid Line Solenoid 3 - Comp 2, Circuit 1

523

523-500 Liquid Line Solenoid 4 - Comp 2, Circuit 2

526

526-527 Common Volt Free Alarm N/O Contact

527