Condensing units, Troubleshooting – Airedale Condensing Units (CU) 3kW - 80kW User Manual

Page 23

Advertising
background image

Condensing Units

CUS 15 - 60 / HCU 20 – 30D

Chillers & Condensing Units

Installation & Maintenance:Part No: 6259592 IM 07/14

23

Troubleshooting

REFRIGERATION

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Head pressure too high.

Condenser coil blocked or dirty

Clean condenser coil

Head pressure controller faulty.

Check fan speed controller - if faulty -
replace.

Fan not operating or operating inefficiently. Check motor - if faulty - replace.

Head pressure too low.

Fan operating too fast in low ambient
conditions.

Check fan speed controller adjustment - if
faulty - replace.

Compressor short cycles or
LP cut-out operated.

LP switch set too high.

Adjust/replace as appropriate.

Lack of refrigerant (bubbles in sight glass
only as indication).

Check for leaks

– reclaim refrigerant,

repair, evacuate and recharge system.

Clogged filter drier (pressure / temperature
drop across it).

Replace once the cause has been
identified and rectified.

Condenser fan running at full speed in
winter (full airflow).

Check fan speed controller setting - if faulty
- replace.

Suction Pressure too low.

Low evaporator airflow (not Airedale Unit).

Check fan motors, belts and drives.

Flash gas (bubbles in sight glass) at
expansion valve.

Investigate for refrigerant leaks, repair and
re-charge system.

Clogged filter drier (pressure / temperature
drop across it).

Replace.

Obstruction in liquid line solenoid valve.

Pump down, inspect, clean or replace.

Obstruction in expansion valve.

Pump down, inspect, clean or replace.