Condensing Units

CUS 15 - 60 / HCU 20 – 30D

Chillers & Condensing Units

Installation & Maintenance:Part No: 6259592 IM 07/14

19

Commissioning Procedure

– Example

CONDENSERS/CONDENSING

UNITS - C/CUS/CUHS/HCU/CFCUS

Ai r e d a l e I n t e r n a t i o n a l

Ai r C o n d i t i o n i n g L t d

TO BE COMPLETED IN CONJUNCTION WITH COMMISSIONING PROCEDURE

RETURN WHITE COPY TO AIREDALE/RETAIN PINK COPY

Leeds Road, Rawdon, Leeds

LS19 6JY ENGLAND

Tel: 0113 239 1000

Fax: 0113 250 7219

Engineer:

Company:

Date:

Model:

Serial No:

Site Ref:

1

Pre Commissioning Checklist

1.1

Unit Condition Satisfactory

Comment:

1.2

Holding charge retained

Circ 1

Yes/No Circ 2

Yes/No

1.3

Electrical connections tight

V

1.4

Voltage at mains supply

L1-L2

V L2-L3

V L3-L1

V

1.5

System pressure test:

I

Initial test pressure

Circ 1

Barg

Circ 2

Barg

ii

Final test pressure

Circ 1

Barg

Circ 2

Barg

iii

Test duration

Circ 1

Hrs

Circ 2

Hrs

2

Commissioning Checklist

2.1

Final system vacuum

Circ 1

mBar

Circ 2

mBar

2.2

Vacuum hold time

Circ 1

Min

Circ 2

Min

2.3

Refrigerant type

2.4

Refrigerant charge

Circ 1

kg

Circ 2

kg

2.5

Timer settings correct and operational (if fitted)

Low pressure override - 3mins

Circ 1

Mins

Circ 2

Mins

Defrost - 30 mins

Circ 1

Mins

Circ 2

Mins

Anti cycle timer -10 mins

Circ 1

Mins

Circ 2

Mins

2.6

Head pressure control set

Circ 1

Barg

Circ 2

Barg

2.7

HP/LP switch cut outs:

Circ 1

Barg

Circ 2

Barg

I

LP cut out - 2.0 barg

LP Cut Out

Barg

LP Cut Out

Barg

ii

LP cut in - 3.0 barg

LP Cut In

Barg

LP Cut In

Barg

iii

HP cut out - 27.0 barg

HP Cut Out

Barg

HP Cut Out

Barg

2.8

HGBP valve setting (if fitted)

Circ 1

Barg

Circ 2

Barg

2.9

Superheat at compressor

Circ 1

°C

Circ 2

°C

2.10 Added oil volume (if applicable)

Circ 1

Lt

Circ 2

Lt

2.11 Operating conditions:

i

Suction pressure

Circ 1

Barg

Circ 2

Barg

ii

Discharge pressure

Circ 1

Barg

Circ 2

Barg

2.12 Compressor Amps

(CU & CFCU)

L1

Amps

L1

Amps

L2

Amps

L2

Amps

L3

Amps

L3

Amps

2.13 Condenser Fan Amps

/

/

Amps

/

/

Amps

3

Other comments

IMPORTANT: THIS IS AN IMPORTANT WARRANTY DOCUMENT AND WARRANTY COULD BE

INVALIDATED SHOULD AIREDALE NOT HOLD A COPY ON FILE.

QTYENG 10 - 08/98