Condensing units, Troubleshooting – Airedale Condensing Units (CU) 3kW - 80kW User Manual

Page 22

Advertising
background image

CUS 15 - 60 / HCU 20 – 30D

Condensing Units

Chiller & Condensing Units

Installation & Maintenance:Part No: 6259592 IM 07\14

22

Troubleshooting

GENERAL

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Compressor not operating.

No power to compressor

Check isolator, fuses, MCBs, contactor and
control circuit wiring

Low pressure switch operated (large or
complete loss of refrigerant charge).

Recover refrigerant, repair, evacuate and
recharge system.

Compressor thermal protection device
operated

Check if compressor overheated - possibly
short of refrigerant

Condenser fan thermal trip open circuit

Investigate and correct.

Seized compressor, possibly due to lack of
oil.

Replace compressor - investigate oil
trapping and general installation.

Defective compressor motor.

Check winding resistances - replace
compressor. If burnt out follow burn out
procedure using suction line burn-out drier.

Noisy Compressor.

Lack of oil.

Repair leaks if any, add oil if required but
not too much - remember too much is as
bad as too little. Investigate pipe system
and trapping.

Best method to pump down to see if oil can
be encouraged back. If no oil still, drain
compressor and measure in correct
quantity.

Expansion valve stuck in open position
(abnormally cold suction line).

Ensure feeler bulb is tight on suction and
superheat is correct (normally 5

°

C to 6

°

C.). Replace power assembly or valve as

necessary.

Worn or scored compressor bearing.
(excessive knocking).

Replace compressor.

Head Pressure too high.

Condenser coil clogged or dirty.

Clean condenser.

Air or other non-condensable gas in
system.

Evacuate system and re-charge with new
refrigerant.

Overcharge of refrigerant.

Remove excess refrigerant from system by
recovery system.