Condensers & Condensing Units

Technical Manual : Part No 904-047 V1.4.0_02_2013

Performance Data

OPERATING LIMITS

Cooling

Standard Unit with Electronic Fan Speed Control (-20°C)

Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C

Refer to

Performance Data - Capacity Data

Minimum Evaporating Temperature °C

-5°C

Maximum Evaporating Temperature °C

+10°C

1

For conditions outside those quoted, please refer to Airedale.

SOUND DATA

Measurement of Sound
Data

All sound data quoted has been measured in the third-octave band limited values, using
a Real Time Analyser calibrated sound intensity meter in accordance with
BS EN ISO9614 Part 1 : 1995. The Global sound data quoted is valid for noise
emitted in the horizontal plane in all directions

All Sound Power Levels quoted are calculated from measured sound intensity according
to BS EN ISO9614 Part 1 : 1995.

Sound Pressure Levels are calculated from sound power using the expanded
parallelepiped method according to BS EN ISO11203 : 1996.

Sound Directivity

The Global sound measurements quoted in the following tables do not incorporate any
directivity or denote any sound level heard at any given position surrounding the
condensing unit, rather they represent the total sound level radiating from the chiller in
all directions in the horizontal plane from source.

Using the adjustment factors from the map below, specific directional sound power levels
can be derived from the global sound power data.


- 11.0

- 4.0

- 11.0

- 4.0

Example - UCCU250DSQ-8/2, Sound Power of 82 dB(A)
=