Controls, Condensing units ultima compact – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual

Page 9

Advertising
background image

Condensing Units

ULTIMA COMPACT

Condensers & Condensing Units

9

Technical Manual : Part No 904-047 V1.4.0_02_2013

Controls

GENERAL
DESCRIPTION

The

microprocessor controller offers powerful analogue and digital control to

meet a wide range of monitoring and control features including a real time clock and
Industry standard communication port and network connections.

The controller’s inbuilt display is used for viewing the unit operating status and making
adjustments to control parameters by allowing the operator access to a series of
display pages.

Also featured are a visual alarm and the facility to adjust and display control settings by
local operator for information and control.

DISPLAY/KEYPAD

5

3

6

2

1

4

08:44 13/05/02 Mst
Remote 0-10V Input
Signal Voltage 05.6V
Unit ON

7

Esc

Prg

1 UP/DOWN KEYS

To change Adjustable Fields & Scrolls
up & down available Menus

2 ENTER

Selects Menus & Moves Cursor to
Adjustable Fields Green LED

3 ESC

Green LED lit when Operating Page
displayed, Returns to Operating Page
Screen when pressed

4 PROGRAM

Opens the Available Menus

5 ALARM

Red LED Indicates Alarm Present

6 4 ROW LCD DISPLAY
7 CURSOR (FLASHING): Top Left

Position =

“HOME” Indicates adjustable

Fields

CONTROL
MANAGEMENT

Airedale recognises that all applications differ and have provided 4 of the most common
to select via the microprocessor:

External 0-10V Signal

The compressor operation is controlled by the microprocessor in response to an external
0-10V analogue signal.

Suction Pressure
Monitoring

The compressor operation is controlled by the microprocessor in response to changes in
the measured suction pressure.

Remote Space
Temperature Sensor

The compressor operation is controlled by the microprocessor in response to changes in
return air temperature, measured via a remote sensor (supplied loose).

Remote Digital Inputs

Offering the user complete control of the cooling provided by the unit, via a number (1-6)
of digital signals (corresponding to the number of stages of cooling).

FEATURES

Unit Remote ON/OFF

Disables/Enables the condensing unit remotely.

Compressor Anti Cycle
Control

Automatic via the Microprocessor.

Compressor Load Limit

Limits the condensing pressure by unloading above 24barg.

Limits the evaporating pressure by unloading at the minimum pressure setpoint.

Compressor Hours Run

Displays hours run of each compressor.

Password Protection

The control system integrity can be maintained by restricting access with a password
PIN number.

CAUTION

IMPORTANT: To change the PIN number, please contact Airedale at time of order
with the preferred 4 digit number.