Interconnecting wiring, Condensing units ultima compact, Conde nsing units – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual

Page 35: Ultima com pact, Installation data, Condensers & condensing units, Single circuit, Double circuit

Advertising
background image

Condensing Units

ULTIMA COMPACT

Condensers & Condensing Units

35

Technical Manual : Part No 904-047 V1.4.0_02_2013

Conde

nsing

Units

ULTIMA

COM

PACT

Installation Data

INTERCONNECTING WIRING

Single Circuit

(not including: leak detector,
and remote setpoint adjust)

UCCU30

UCCU80

(Excluding

UCCU75)

L1

 

Mains incoming supply 400V/3PH/50Hz 50Hz
(N2 Only Required For UCCU30-80Q/DQ & UCCU50-60SSQ/DSQ)

L2

 

L3

 

N2

 

E

 

L4

 

Separate Permanent Supply 230V/1PH/50Hz

N1

 

E

 

502

 

Circuit 1 24VAC (Suction Pressure Control Option), Compressor.1 24VAC (Digital
I/P Control Option)

504

 

502

 

Remote On/Off 24VAC, Compressor.2 24VAC (Digital I/P Control Option)

505

 

500

 

0 v

Remote Capacity Control (0-10VDC Control Option)

806

 

0-10v

52

 

Circuit 1 Solenoid Valve

53

 

Volt Free Contact N/O

573

 

Circuit 1

Volt Free Common Alarm

574

 

Volt Free Alarm N/O

575

 

Volt Free Alarm N/C

RX-/TX-

 

RX+/TX+

 

/ Optional EEV Connections

GND

 

Double Circuit

UCCU30

UCCU450

L1

 

Mains incoming supply 400V/3PH/50Hz
(N2 Only Required For UCCU30-80Q/DQ & UCCU50-60SSQ/DSQ)

L2

 

L3

 

N2

 

E

 

L4

 

Separate Permanent Supply 230V/1PH/50Hz

N1

 

E

 

502

 

Circuit 1 24VAC (Suction Pressure Control Option) / Compressor.1 24VAC (Digital
I/P Control Option)

504

 

502

 

Unit Remote On/Off 24VAC, Circuit 2 24VAC (Suction Pressure Control Option),
Compessor.2 24VAC (Digital I/P Control Option)

505

 

502

 

Compressor.3 24VAC (Digital I/P Control Option)

506

 

502

 

Compressor.4 24VAC (Digital I/P Control Option)

507

 

502

 

Compressor.5 24VAC (Digital I/P Control Option UCCU275-450 Only Excluding
UCCU250)

508

 

502

 

Compressor.6 24VAC (Digital I/P Control Option UCCU275-450 Only Excluding
UCCU250)

509

 

502

 

Remote On/Off 24VAC, Compressor.2 24VAC (Digital I/P Control Option)

505

 

500

 

0 v

Remote Capacity Control (0-10VDC Control Option)

806

 

0-10v

52

 

Circuit 1 Solenoid Valve

53

 

Volt Free Contact N/O

54

 

Circuit 2 Solenoid Valve

55

 

Volt Free Contact N/O

573

 

Circuit 1

Volt Free Common Alarm

574

 

Volt Free Alarm N/O

575

 

Volt Free Alarm N/C

576

 

Circuit 2

Volt Free Common Alarm

Dual Circuit Only

577

 

Volt Free Alarm N/O

578

 

Volt Free Alarm N/C

RX-/TX-

 

/ Optional EEV Connections

RX+/TX+

 

GND

 