Condensing units ultima compact, General specification, Condensers & condensing units – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual

Page 25: Electrical data

Advertising
background image

Condensing Units

ULTIMA COMPACT

Condensers & Condensing Units

25

Technical Manual : Part No 904-047 TM E 12/04/D

General Specification

ELECTRICAL DATA

UCCU300D-8/2

UCCU330D-10/2

UCCU360D-10/2

UCCU400D-12/2

UCCU450D-12/2

Unit Data

Nominal Run Amps

(1) A

173

231

252

279

303

Maximum Start Amps

(2) A

454

462

483

552

576

Permanent Supply

VAC

230 V 1 PH 50 Hz

Mains Supply

VAC

400 V 3 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Rec Mains Fuse Size

A

250

250

315

315

355

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Control Circuit

VAC

24V/230V AC

Condenser Fan - Per Fan

Quantity

8

10

10

12

12

Full Load Amps

A

1.75

1.75

1.75

1.75

1.75

Locked Rotor Amps

A

6.20

6.20

6.20

6.20

6.20

Motor Rating

kW

0.98

0.98

0.98

0.98

0.98

Compressor - Per Compressor

Quantity

4

3 + 3

6

3 + 3

6

Motor Rating

kW

22.8

18.2 / 15.0

18.2

22.8 / 18.2

22.8

Nominal Run Amps

(1) A

47.0

39.0 / 32.0

39.0

47.0 / 39.0

47.0

Sump Heater Rating

W

130.0

130.0 / 130.0

130.0

130.0 / 130.0

130.0

Start Amps

(2)

320.0

270.0 / 215.0

270.0

320.0 / 270.0

320.0

Type Of Start

Direct on line

QUIET DQ

UCCU300DQ-10/2

UCCU330DQ-12/2

UCCU360DQ-12/2

UCCU400DQ-14/2

UCCU450DQ-14/2

All data as above except:

Condenser Fan - Per Fan

Quantity

10

12

12

14

14

Full Load Amps

A

1.15

1.15

1.15

1.15

1.15

Locked Rotor Amps

A

2.10

2.10

2.10

2.10

2.10

Motor Rating

kW

0.70

0.70

0.70

0.70

0.70

SUPER QUIET DSQ

UCCU300DSQ-12/2 UCCU330DSQ-14/2 UCCU360DSQ-14/2 UCCU400DSQ-16/2 UCCU450DSQ-16/2

All data as above except:

Condenser Fan - Per Fan

Quantity

12

14

14

16

16

Full Load Amps

A

0.83

0.83

0.83

0.83

0.83

Locked Rotor Amps

A

1.50

1.50

1.50

1.50

1.50

Motor Rating

kW

0.32

0.32

0.32

0.32

0.32

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1) A

158

207

228

246

261

Maximum Start Amps

(2) A

442

362

483

552

576

Recommended Mains Fuse

A

200

250

250

250

315

Compressor Nominal Run Amps
- Per Compressor

A

4 x 36

3 x 30 / 3 x 24

6 x 30

3 x 36 / 3 x 30

6 x 36

Electronic Soft-start

Nominal Run Amps

(1) A

173

231

252

279

303

Maximum Start Amps

(2) A

314

354

375

424

448

Recommended Mains Fuse

A

250

250

315

315

355

(1)

Based at 7.2°C Evaporating and 54.4°C Condensing temperatures.

(2)

Starting amps refers to the direct on line connections.