Ultima compact condensing units, General specification, Condensers & condensing units – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual

Page 24: Electrical data

Advertising
background image

ULTIMA COMPACT

Condensing Units

24

Condensers & Condensing Units

Technical Manual : Part No 904-047 V1.4.0_02_2013

General Specification

ELECTRICAL DATA

UCCU160D-4/2

UCCU180D-6/2

UCCU200D-6/2

UCCU225D-6/2

UCCU250D-6/2

UCCU275D-8/2

Unit Data

Nominal Run Amps

(1) A

115

132

146

158

172

160

Maximum Start Amps

(2) A

264

315

377

389

403

440

Permanent Supply

VAC

230 V 1 PH 50 Hz

Mains Supply

VAC

400 V 3 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

16

Rec Mains Fuse Size

A

125

160

160

200

200

200

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Control Circuit

VAC

24V/230V AC

Condenser Fan - Per Fan

Quantity

4

6

6

6

6

8

Full Load Amps

A

2.70

2.70

2.70

2.70

2.70

1.75

Locked Rotor Amps

A

7.00

7.00

7.00

7.00

7.00

6.20

Motor Rating

kW

1.60

1.60

1.60

1.60

1.60

0.98

Compressor - Per Compressor

Quantity

4

2 + 2

2 + 2

2 + 2

4

2 + 2

Motor Rating

kW

11.7

15.0 / 11.7

18.2 / 11.7

18.2 / 15.0

18.2

22.8 / 18.2

Nominal Run Amps

(1) A

26.0

32.0 / 26.0

39.0 / 26.0

39.0 / 32.0

39.0

47.0 / 39.0

Sump Heater Rating

W

75.0

130.0 / 75.0

130.0 / 75.0

130.0 / 130.0

130.0

130.0 / 130.0

Start Amps

(2)

175.0

215.0 / 175.0

270.0 / 175.0

270.0 / 215.0

270.0

320.0 / 270.0

Type Of Start

Direct on line

QUIET DQ

UCCU160DQ-6/2

UCCU180DQ-6/2

UCCU200DQ-6/2

UCCU225DQ-8/2

UCCU250DQ-8/2

UCCU275DQ-10/2

All data as above except:

Condenser Fan - Per Fan

Quantity

6

6

6

8

8

10

Full Load Amps

A

1.25

1.25

1.25

1.25

1.25

1.15

Locked Rotor Amps

A

4.50

4.50

4.50

4.50

4.50

2.10

Motor Rating

kW

0.69

0.69

0.69

0.69

0.69

0.70

SUPER QUIET DSQ

UCCU160DSQ-6/2

UCCU180DSQ-6/2

UCCU200DSQ-8/2

UCCU225DSQ-8/2

UCCU250DSQ-8/2 UCCU275DSQ-12/2

All data as above except:

Condenser Fan - Per Fan

Quantity

6

6

8

8

8

12

Full Load Amps

A

0.78

0.78

0.78

0.78

0.78

0.83

Locked Rotor Amps

A

1.50

1.50

1.50

1.50

1.50

1.50

Motor Rating

kW

0.48

0.48

0.48

0.48

0.48

0.32

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1) A

103

118

132

142

156

146

Maximum Start Amps

(2) A

264

315

377

389

403

430

Recommended Mains Fuse

A

125

125

160

160

200

200

Compressor Nominal Run Amps
- Per Compressor

A

4 x 20

2 x 24 / 2 x 20

2 x 30 / 2 x 20

2 x 30 / 2 x 24

4 x 30

2 x 36 / 2 x 30

Electronic Soft-start

Nominal Run Amps

(1) A

115

132

146

158

172

160

Maximum Start Amps

(2) A

194

229

269

281

295

302

Recommended Mains Fuse

A

125

160

160

200

200

200

(1)

Based at 7.2°C Evaporating and 54.4°C Condensing temperatures.

(2)

Starting amps refers to the direct on line connections.