Condensing units ultima compact, General specification, Condensers & condensing units – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual

Page 23: Electrical data

Advertising
background image

Condensing Units

ULTIMA COMPACT

Condensers & Condensing Units

23

Technical Manual : Part No 904-047 TM E 12/04/D

General Specification

ELECTRICAL DATA

UCCU75D-2/1

UCCU100D-2/1

UCCU110D-4/2

UCCU125D-3/1

UCCU130D-4/2

UCCU150D-3/1

Unit Data

Nominal Run Amps

(1) A

54

68

75

89

95

109

Maximum Start Amps

(2) A

140

172

179

238

244

258

Permanent Supply

VAC

230 V 1 PH 50 Hz

Mains Supply

VAC

400 V 3 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

16

Rec Mains Fuse Size

A

63

80

100

125

125

125

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

70 (Direct to

MCCB)

70 (Direct to

MCCB)

Direct to Bus Bar

70 (Direct to

MCCB)

Direct to Bus Bar

70 (Direct to

MCCB)

Control Circuit

VAC

24V/230V AC

Condenser Fan - Per Fan

Quantity

2

2

4

3

4

3

Full Load Amps

A

1.75

1.75

2.70

1.75

2.70

1.75

Locked Rotor Amps

A

6.20

6.20

7.00

6.20

7.00

6.20

Motor Rating

kW

0.98

0.98

1.60

0.98

1.60

0.98

Compressor - Per Compressor

Quantity

4

4

4

2 + 2

2 + 2

4

Motor Rating

kW

6.2

8.1

8.1

8.1 / 11.7

8.1 / 11.7

11.7

Nominal Run Amps

(1) A

12.7

16.1

16.1

16.1/ 26.0

16.1 / 26.0

26.0

Sump Heater Rating

W

65.0

65.0

65.0

65.0 / 75.0

65.0 / 75.0

75.0

Start Amps

(2)

98.0

120.0

120.0

120.0 / 175.0

120.0 / 175.0

175.0

Type Of Start

Direct on line

QUIET DQ

UCCU75DQ-2/1

UCCU100DQ-2/1

UCCU110DQ-4/2

UCCU125DQ-3/1

UCCU130DQ-4/2

UCCU150DQ-4/1

All data as above except:

Condenser Fan - Per Fan

Quantity

2

2

4

3

4

4

Full Load Amps

A

1.15

1.15

1.25

1.15

1.25

1.15

Locked Rotor Amps

A

2.10

2.10

4.50

2.10

4.50

2.10

Motor Rating

kW

0.68

0.68

0.69

0.68

0.69

0.68

SUPER QUIET DSQ

UCCU75DSQ-3/1

UCCU100DSQ-3/1

UCCU110DSQ-4/2

UCCU125DSQ-4/1

UCCU130DSQ-6/2

UCCU150DSQ-4/1

All data as above except:

Condenser Fan - Per Fan

Quantity

A

3

3

4

4

6

4

Full Load Amps

A

0.83

0.83

0.78

0.83

0.78

0.83

Locked Rotor Amps

A

1.50

1.50

1.50

1.50

1.50

1.50

Motor Rating

kW

0.32

0.32

0.48

0.32

0.48

0.32

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1) A

49

61

68

80

86

97

Maximum Start Amps

(2) A

140

172

179

238

244

258

Recommended Mains Fuse

A

63

80

100

125

125

125

Compressor Nominal Run Amps
- Per Compressor

A

4 x 11

4 x 13

4 x 13

2 x 20 / 2 x 13

2 x 20 / 2 x 13

4 x 20

Electronic Soft-start

Nominal Run Amps

(1) A

54

68

75

89

95

109

Maximum Start Amps

(2) A

100

124

131

168

174

188

Recommended Mains Fuse

A

63

80

100

125

125

125

(1)

Based at 7.2°C Evaporating and 54.4°C Condensing temperatures.

(2)

Starting amps refers to the direct on line connections.