Configurable Settings

Applicability

Factory default

Trend indicator (display)

HF63, HF65

Enabled

Communication protocol

HF65

RO-ASCII

RS-485 address

HF65

0

TCP/IP settings

HF65

See document E-M-TCPIP-Conf

Device name

HF63, HF65

Instrument model

Functions

Applicability

Factory default

Humidity / temperature adjustment

K HF63, HF65

Device write protection

HF63, HF65

Disabled

Menu access from keypad

HF63, HF65

Enabled

Limit humidity output to 100 %RH

HF63, HF65

Enabled

Out-of-limit value digital / display alarm

HF63, HF65

Disabled

Data recording

K HF63, HF65

Enabled (loop mode – 10 min. interval)

Automatic humidity sensor test

HF63, HF65

Disabled

Humidity sensor drift compensation

HF63, HF65

Disabled

Fail safe mode

HF63, HF65

Disabled

Simulator mode

HF63, HF65

Disabled


o

For a detailed description of all AirChip 3000 / HF6 main functions see document E-T-AC3000-DF-V1

o

Instructions regarding the configuration of the HF6 and access to its functions are provided in the
following manuals:

E-M-HW4v2-F2-008
E-M-HW4v2-Main
(§ 6.5)
E-M-HW4v2-DR-001
E-M-HW4v2-A2-001
E-M-AC3000-CP
.

o

Instructions for configuring the TCP/IP settings of the HF65, are provided in document
E-M-TCPIP-Conf

o

The factory default setting for dew / frost point calculation is frost point below freezing

5

Mechanical installation

5.1 General guidelines

Relative humidity is extremely dependent on temperature. Proper measurement of relative humidity requires
that the probe and its sensors be at exactly the temperature of the environment to be measured. Because of
this, the location where you choose to install the probe can have a significant effect on the performance of the
instrument. The following guidelines should guarantee good instrument performance:

a) Select a representative location: install the probe where humidity, temperature and pressure

conditions are representative of the environment to be measured.

b) Provide good air movement at the probe: air velocity of at least 200 ft/ minute (1 meter/second)

facilitates adaptation of the probe to changing temperature.