Electrical diagram 15 to 40 VDC or 12 to 28 VAC power supply with current outputs












Electrical diagram 85 to 265 VAC power supply with current outputs













The maximum permissible cable length, connecting the unit to other devices, is determined by the total
resistance resulting from the addition of the cable resistance and that of the devices connected in series with
the unit. This resistance should not exceed 500 ohms.

Terminal block diagram

Terminals

Description

K6-1: -►

General ground (see note below)

K6-2: +

Power supply: 15…40 VDC (+)
or VAC - Phase

K6-3: -

Power supply (-) or VAC - neutral

Terminals

Description

K2-1: OUT 1

Relative humidity or dew point (+)

K2-2: OUT 2

Temperature output (+)

K2-3: GND

Ground (tied with other GND)

K2-4: GND

Ground (tied with other GND)