6.4 Wiring

6.4.1

HF631 to HF63A: 3-wire analog transmitter


Electrical diagram 15 to 40 VDC or 12 to 28 VAC power supply with voltage outputs












Electrical diagram 85 to 265 VAC power supply with voltage outputs











The maximum permissible cable length can be determined under consideration of the voltage drop caused by
the current flowing to the devices connected to the unit. The voltage drop in the cable depends both on cable
resistance and on the equivalent resistance of the devices connected in parallel to the unit. The total
resistance connected to each unit output should be at least 1000 ohms. Cable resistance should not be more
than 1/1000 of the load resistance.