HygroFlex HF63/HF65 Humidity Temperature
Transmitters: User Guide

Document title

Page 22 of 34

© 2008; Rotronic AG E-M-HF63_65-V1_11

In the situation where the external device uses an internal pull-up resistor the value of this resistor should
meet the requirements shown below. It is also necessary to add a pull-down resistor RL connected to ground
in order to be able to read 100% of the range of the HF63 voltage output.

















R Pull-up

RL

GND

VCC

Voltage Output

HF63

HF63 signal

VCC

R pull-up

RL

0…1V 3.3V

≥ 250 kOhm

1 kOhm

HF63 signal

VCC

R pull-up

RL

0…1V 5.0V

≥ 400 kOhm

1 kOhm

0…5V 5.0V

≥ 400 kOhm

5 kOhm

HF63 signal

VCC

R pull-up

RL

0…1V 10.0V

≥ 1 MOhm

1 kOhm

0…5V 10.0V

≥ 1 MOhm

5 kOhm

0…10V 10.0V

≥ 1 MOhm

10 kOhm



7.2 HF63 transmitters (analog outputs)

If so desired use the HW4 software to configure the HF6. Complete the mechanical and electrical installation
and simply power up the HF6.

7.3 HF65 (digital output)


Configuration and full access to all HF65 functions requires a PC with the ROTRONIC HW4 software installed.

Starting with firmware version 1.3, the HF65 offers several communication protocol options that allow users to
read the measurement data without the HW4 software. When using the standard RO-ASCII protocol, access
to some of the HF65 functions is also possible without HW4. For details, see document E-M-AC3000-CP.

IMPORTANT: Depending on the type of digital interface, either the PC or the HF45 must be configured
by the user as indicated below.

a) USB network connection


Prior to connecting the HF65 to a USB port you must install the ROTRONIC USB driver on the HW4 PC. For
instructions see the HW4 manual E-M-HW4v2-Main (§ 6.3)

b) Ethernet (TCP/IP) network connection (wired or wireless)


Prior to connecting the HF65 to an active Ethernet network you must configure the HF65 TCP/IP settings. For
instructions see the HW4 manual E-M-HW4v2-Main (§ 6.4) and technical note E-M-TCPIP-Conf

WARNING
: Connecting a device to an active Ethernet network can disrupt communications on the network.
Before connecting the HF65, make sure that it is properly configured for your network