TOHO ELECTRONICS TTM-339 User Manual

Page 22

Advertising
background image

- 22 -


5.5

Common parameter setting mode SET 4 (1)

SET04

Name

Setting content

Initial value

1

SLH SV limiter upper limit (*2) (*3)

Thermocouple/RTD input (SLL + 5.0) to SV setting range upper limit (

C)

(SLL + 5) to SV setting range upper limit (

C)

1200

Current/voltage input (SLL + 50) to SV setting range upper limit (digit)

12000

2

SLL SV limiter lower limit (*2) (*3)

Thermocouple/RTD input SV setting range lower limit to (SLH - 5.0) (

C)

SV setting range lower limit to (SLH - 5) (

C)

0

Current/voltage input (SLH - 50) to SV setting range lower limit (digit)

3

CNT Control type setting

1 Primary...pid control

Secondary---None

1

2 Primary---onoff control

Secondary---None

3 Primary---pid control

Secondary---pid control

4 Primary---pid control

Secondary---onoff control

5 Primary---onoff control

Secondary---onoff control

4

DIR Forward/reverse operation setting

0 Reverse operation

0

1 Forward operation

5

MV1 Primary control operating amount

0.0 to 100.0 (%)

0.0

6

TUN Tuning type setting

1 Primary auto-tuning

1

2 Secondary auto-tuning
3 Primary/secondary auto-tuning

7

ATG AT coefficient setting

0.1 to 10.0 (times)

1.0

8

ATC AT sensitivity setting

Thermocouple/RTD input 0.0 to 999.9 (°C) 0 to 999 (°C)

2

Voltage/current input 0 to 9999 (digit)

9

AT1 AT startup screen for PID No. 1 (low

temperature)

Startup starts/stops by setting a SV and using the RUN/STOP key.
Characters and PV are alternately displayed in the PV digit during AT.
The SV range is SLL to PM1.

0

10

AT2 AT startup screen for PID No. 2

(intermediate temperature)

Startup starts/stops by setting a SV and using the RUN/STOP key.
Characters and PV are alternately displayed in the PV digit during AT.
The SV range is PM1 to PM2.

0

11

AT3 AT startup screen for PID No. 3 (high

temperature)

Startup starts/stops by setting a SV and using the RUN/STOP key.
Characters and PV are alternately displayed in the PV digit during AT.
The SV range is PM2 to SLH.

10

12

ATALL AT startup screen for PID No. 1~3

Use the RUN/STOP key for start and stop.
During the auto tuning, Character//PV is alternately displayed at PV
display, and No. 1 – 3/SV are alternately displayed at SV display.

13

P1 Proportional band setting for PID No. 1 (low temperature)

0.1 to 200.0 (%)

3.0

14

I1 Integral time setting for PID No. 1 (low temperature)

0 to 3600 (seconds)

0

15

D1 Derivative time setting for PID No. 1 (low temperature)

0 to 3600 (seconds)

0

16

PM1 Intermediate point 1 setting for the

PID range

Thermocouple/RTD input SLL to SLH- 5.0 (

C) SLL to SLH - 5 (

C)

0

Current/voltage input SLL to SLH - 50 (digit)

0

17

P2 Proportional band setting for PID No. 2 (intermediate

temperature)

0.1 to 200.0 (%)

3.0

18

I2 Integral time setting for PID No. 2 (intermediate temperature) 0 to 3600 (seconds)

0

19

D2 Derivative time setting for PID No. 2 (intermediate

temperature)

0 to 3600 (seconds)

0

20

PM2 Intermediate point 2 setting for the PID range

PM1 to SLH (

C)

10

21

P3 Proportional band setting for PID No. 3 (high temperature)

0.1 to 200.0 (%)

3.0

22

I3 Integral time setting for PID No. 3 (high temperature)

0 to 3600 (seconds)

0

23

D3 Derivative time setting for PID No. 3 (high temperature)

0 to 3600 (seconds)

0

24

T1 Primary control proportional cycle

0.1 to 120.0 (seconds)

1.0

25

ARW Anti-reset windup

0.0 to 110.0 (%) Function turned off at 110.0 (%) setting

110.0

26

PS1 Primary control loop abnormalityPV

variation setting

Thermocouple/RTD input 0.0 to 999.9 (

C) or 0 to 999 (

C)

0

Current/voltage input 0 to 9999 (digit)

27

LOP1 Primary control loop abnormality time

setting

0 to 3600 (seconds)

0

28

CMOD Primary control off-point position

selection setting

0 SV unit setting

0

1 Upper

2 Middle

3 Lower

29

C1 Primary control sensitivity control

Thermocouple/RTD input 0.0 to 999.9 (

C) 0 to 999 (

C)

1

Current/voltage input 0 to 9999 (digit)

10

30

CP1 Primary control off-point position

Thermocouple/RTD input -999.9 to 999.9 (

C) -999 to 999 (

C)

0

Current/voltage input -9999 to 9999 (digit)