3. Terminal connection diagram

Power supply

100 to 240 VAC

A

Communications RS-485

EV4

Open collector

output

B

TS1

Not in use

Pattern 1

No-voltage

contact input

TS2

OUT1

(Relay/SSR/4 -20

mADC)

C

Pattern 2

TS3

NO

Pattern 3

TS4

OUT2(None/Relay/

SSR/

4 -20 mADC)

C

Pattern 4

TIME

NO

RUN/RDY

COM

Not in use

Operation

switchover

CT input

Relay contact

output

EV1

Step feed

EV2

COM

Sensor input

* See below.

EV3

END signal

Relay contact

output

COM

COM

RTD

TC/10 mV

Current/voltage

b

B

A

Precautions on wiring

Warning

Do not turn on the power until all wiring is complete in order to prevent an electric shock
or equipment failure.

★ For inputs from a thermocouple, use the specified wires or compensating leads.
★ For inputs from a resistance temperature detector, use wires that the wire resistance of leads is small and no resistance difference

is present among 3 wires (3-wire type).

★ Provide input signal lines distant from power supply lines, power lines or load lines so as not to affect input signal lines with

noise induction.

★ Wire the power supply for instruments such that they do not receive noises from the power supply for power devices.

The use of a noise filter is recommended in case that the equipment is vulnerable to noises.
Take care the following when a noise filter is used.
◎ Install the noise filter as close to a temperature controller as possible.

Wire the instruments in as short a distance as possible to output lines (secondary side) of the noise filter and power
terminals for the temperature controller.

◎ Isolate the noise filter input line (primary side) from its output line (secondary side).

High-frequency elements of noises may be induced, resulting in no provision of much noise attenuation effect as expected,

in case of input and output wires being close one another, such as being bundled together or installed in a same duct or
tube.

◎ Wire the grounding wire of the noise filter in as short a distance as possible.

A long grounding wire is equivalent to insert of an inductance, resulting in deteriorated high-frequency characteristics.

◎ Before installing the noise filter, peel off the paint applied on a mounting plate of the noise filter as appropriate, in order to

reduce the contact resistance between the noise filter and equipment housing.


★ For the power supply, use and twist wires that cause less voltage drop.
★ For the equipment being activated, it takes about 4 seconds after its power turns on. Use delay relays when using the

equipment for generating signals for interlocking circuits.

★ The equipment is not attached with power supply switch fuses. Separately install fuses in proximity of the equipment, as

needed.
◎ Recommended fuse rating: Rated voltage of 250 V and rated current of 1 A

★ Use crimping terminals that match screw sizes.

◎ Size of crimping terminal: Terminal width of 6 mm or smaller

Crimping terminal recommended
Manufacturer: NICHIFU
Model: ICTV-1.25Y-3N (Y terminal)

ICTV-1.25-3S (round terminal)


◎ Tightening torque recommended: 0.5 N

m

◎ Applicable wire

Use wires in sizes suitable for the terminals.