TOHO ELECTRONICS TTM-339 User Manual

Page 24

Advertising
background image

- 24 -

5.6

Common parameter setting mode SET 5 to 8

SET05 to SET08

Name

Setting content

Initial value

1

E*F1 Event function 1 setting

Function

Add-on function

00

*0 None

0* None

*1 Deviation upper and lower limits

1* Hold

*2 Deviation upper limit

2* Standby

*3 Deviation lower limit

3* Delay

*4 Deviation range

4* Hold + standby

*5 Absolute value upper and lower limits

5* Hold + Delay

*6 Absolute value upper limit

6* Standby + Delay

*7 Absolute value lower limit

7* Hold + standby + Delay

*8 Absolute value range

2

E*H Event upper limit setting

Thermocouple/RTD input -1999.9 to 2999.9 (

C) -1999 to 2999 (

C) Note that for

R, B and PR40-20 of thermocouple, the following is to be applied. -1999 to 9999 (

C)

0

Current/voltage input -19999 to 29999 (digit)

3

E*L Event lower limit setting

Thermocouple/RTD input -1999.9 to 2999.9 (

C) -1999 to 2999 (

C) Note that for

R, B and PR40-20 of thermocouple, the following is to be applied. -1999 to 9999 (

C)

0

Current/voltage input -19999 to 29999 (digit)

4

E*C Event sensitivity setting

Thermocouple/RTD input 0.0 to 999.9 (

C) 0 to 999 (

C)

0

Current/voltage input 0 to 9999 (digit)

5

E*T Event Delay timer setting

0 to 9999 (second)

0

6

E*F2 Event function 2 setting

(loop abnormality)

Function

Add-on function

00

*0 Nonexistent

0* None

*1 Existent

1* Hold

7

E*P Event polarity setting

0 Normal open

1 Normal close

0

5.7

Common parameter setting mode SET 9 (1)

SET09

Name

Setting content

Initial value

1

MLF

Operation amount function
setting

0 None

2 Operation amount current limiter(average)

0

1 Operation amount limiter

3 Operation amount current limiter(R.M.S)

With the selection of [MLF =1], the following 2 to 9 are selectable for [CNT =1]; the following 2 to 17 are selectable for [CNT = 3 or 4].
* Below, 2 and 3 are for the operation amount limiter function setting, i.e., effective when 1 is selected.

2

MLH11 Primary control operation amount limiter upper limit 1

MLL11 to 100.0(%)

100.0

3

MLL11 Primary control operation amount limiter lower limit 1

0.0 to MLH11(%)

0.0

* Below, 4 and 5 are for the operation amount limiter function setting, i.e., effective when 2 is selected.

4

MLH21 Primary control operation amount limiter upper limit 2

MLL21 to 100.0(%)

100.0

5

MLL21 Primary control operation amount limiter lower limit 2

0.0 to MLH21(%)

0.0

* Below, 6 and 7 are for the operation amount limiter function setting, i.e., effective when 3 is selected.

6

MLH31 Primary control operation amount limiter upper limit 3

MLL31 to 100.0(%)

100.0

7

MLL31 Primary control operation amount limiter lower limit 3

0.0 to MLH31(%)

0.0

* Below, 8 and 9 are for the operation amount limiter function setting, i.e., effective when 4 is selected.

8

MLH41 Primary control operation amount limiter upper limit 4

MLL41 to 100.0(%)

100.0

9

MLL41 Primary control operation amount limiter lower limit 4

0.0 to MLH41(%)

0.0

* Below, 10 and 11 are for the operation amount limiter function setting, i.e., effective when 1 is selected.

10

MLH12 Secondary control operation amount limiter upper limit 1 MLL12 to 100.0(%)

100.0

11

MLL12 Secondary control operation amount limiter lower limit 1 0.0 to MLH12(%)

0.0

* Below, 12 and 13 are for the operation amount limiter function setting, i.e., effective when 2 is selected.

12

MLH22 Secondary control operation amount limiter upper limit 2 MLL22 to 100.0(%)

100.0

13

MLL22 Secondary control operation amount limiter lower limit 2 0.0 to MLH22(%)

0.0

* Below, 14 and 15 are for the operation amount limiter function setting, i.e., effective when 3 is selected.

14

MLH32 Secondary control operation amount limiter upper limit 3 MLL32 to 100.0(%)

100.0

15

MLL32 Secondary control operation amount limiter lower limit 3 0.0~MLH32(%)

0.0

* Below, 16 and 17 are for the operation amount limiter function setting, i.e., effective when 4 is selected.

16

MLH42 Secondary control operation amount limiter upper limit 4 MLL42 to 100.0(%)

100.0

17

MLL42 Secondary control operation amount limiter lower limit 4 0.0 to MLH42(%)

0.0