TOHO ELECTRONICS TTM-339 User Manual

Page 25

Advertising
background image

- 25 -

5.7

Common parameter setting mode SET 9 (2)

SET09

Name

Setting content

Initial value

With the selection of [MLF = 2,3], the following 18 to 41 are selectable.

18

CM1

CT1 current value monitor

0.0 to 50.0 (A) Displays the average at MLF=2.
Displays the R.M.S at MLF=3.

19

OH01 Operation amount limiter point 1

A point is defined as a location corresponding to the number resulted from
calculation of divided values of SLL to SLH into 10 equal segments
multiplied by the point No.
0.0 to 100.0 (%)

100.0

20

OH02 Operation amount limiter point 2

21

OH03 Operation amount limiter point 3

22

OH04 Operation amount limiter point 4

23

OH05 Operation amount limiter point 5

24

OH06 Operation amount limiter point 6

25

OH07 Operation amount limiter point 7

26

OH08 Operation amount limiter point 8

27

OH09 Operation amount limiter point 9

28

OH10 Operation amount limiter point 10

29

OH11 Operation amount limiter point 11

30

AH01 Current value limiter point 1

Upper current limit at the operation amount limiter point
0.0 to 30.0 (A)

30.0

31

AH02 Current value limiter point 2

32

AH03 Current value limiter point 3

33

AH04 Current value limiter point 4

34

AH05 Current value limiter point 5

35

AH06 Current value limiter point 6

36

AH07 Current value limiter point 7

37

AH08 Current value limiter point 8

38

AH09 Current value limiter point 9

39

AH10 Current value limiter point 10

40

AH11 Current value limiter point 11

41

AHC Current value limiter sensitivity

0.1 to 30.0 (A)

0.2

42 and 43 are always effective; 44 and 45 are selectable when [CNT = 3].

42

OU1 Primary control operation amount

increase rate

0.0 to 549.9 (%): 0.0% indicates the function turned off.

0.0

43

OUTM1 Primary control operation amount

increase time

0 to 3600 (second): 0 indicates no function.

0

44

OU2 Secondary control operation

amount increase rate

0.0 to 549.9 (%): 0.0% indicates the function turned off.

0.0

45

OUTM2 Secondary control operation

amount increase time

0 to 3600 (second): 0 indicates no function.

0