Installation and Wiring

5

NXC-ME260 NetLinx Master-Ethernet Card/Module

Installation and Wiring

This section contains information about configuring the

Program

port, cable configurations,

connector pinouts, and NXC-ME260 installation procedures.

Setting the Program Port DIP Switch

Prior to installing the NXC-ME260, configure the Program port’s communication speed by setting

the baud rate DIP switch (SW1) to the appropriate setting. The Program port’s DIP switch is

located to one side of the Master’s RS232 Program port.

Baud rate settings

The Program port DIP switch is located on the Master card’s circuit board. Use this DIP switch to

set the baud rate used by the Program port for communication. Before programming the Master,

make sure the baud rate you set matches the communication set on either your PC’s COM port or

through your NetLinx Studio 2.1. By default, the baud rate is set to 38,400 (bps).

Program Run Disable (PRD) mode

You can also use the Program Port DIP switch to set the Master card to Program Run Disable

(PRD) mode according to the settings listed in the table below.

Baud Rate Settings

Baud Rate

Position 5 Position 6 Position 7

Position 8

9600 bps

OFF

ON

OFF

ON

38,400 bps (default)

OFF

ON

ON

ON

57,600 bps

ON

OFF

OFF

OFF

115,200 bps

ON

ON

ON

ON

Note the orientation of the DIP Switch and the ON position label.
DIP Switch positions 2,3, and 4 must remain in the OFF position at all times.

PRD Mode Settings

PRD Mode

Position 1

Normal mode (default)

OFF

PRD Mode

ON