Installation and Wiring

6

NXC-ME260 NetLinx Master-Ethernet Card/Module

PRD mode prevents the NetLinx program stored in the Master from running when you power up

the NXC-ME260. PRD mode should only be used when you suspect the resident NetLinx program

is causing inadvertent communication and/or control problems. If necessary, place the Master in

PRD mode and use the NetLinx Studio 2.1 program to resolve the communication and/or control

problems with the resident NetLinx program. Then, download the new NetLinx program and try

again.

Setting the Program Port DIP switch

It is recommended that the baud rate DIP switch be set prior to any installation of the NXC-ME260

card.

1.

Locate the red baud rate DIP switch (FIG. 4).

2.

Set DIP switch positions according to the information listed in the Baud Rate Settings and

PRD Mode Settings tables above.

3.

Follow the procedures outlined in the NXC-ME260 Installation and Mounting

Procedures section on page 15.

If the card has already been installed:

1.

Disconnect the power supply from the 2-pin PWR (green) connector on the Master Card.

2.

Unsecure the NXC-ME260 by unscrewing the two faceplate securing screws (on both sides of

the faceplate) using a Phillips-head screwdriver (FIG. 4).

3.

Carefully slide-out the card and locate the red baud rate DIP switch (FIG. 4).

4.

Set the DIP switch positions according to the information listed in the Baud Rate Settings and

PRD Mode Settings tables (page 5).

5.

Place the Master card back into its’ housing and resecure the two faceplate securing screws.

6.

Reconnect the 12 VDC power supply to the 2-pin PWR connector and apply power.

Think of the PRD Mode (On) equating to a PC’s SAFE Mode setting. This mode
allows a user to continue powering a unit, update the firmware, and download a new
program while circumventing any problems with a currently downloaded program.
Power must be cycled to the unit after activating/deactivating this mode on the rear
Program Port DIP switch #1.

FIG. 4 Component locations on the NXC-ME260