Hp 750 w 48v cs dc power supply (94% efficiency) – HP ProLiant DL385p Gen8 Server User Manual

Page 119

Advertising
background image

Specifications 119

HP 750 W 48V CS DC power supply (94% efficiency)

Specification

Value

Input requirements

Rated input voltage

-36V to -72V DC

-48V DC, nominal input

Rated input frequency

DC

Rated input current

2.3A at -36V DC

12A at -72V DC

17A at -48V DC, nominal input

Rated input power

840 W at -36V DC input
830 W at -72V DC input

820 W at -48V DC, nominal input

Btus per hour

2865 at -36V DC input
2830 at -72V DC input

2796 at -48V DC, nominal input

Power supply output

Rated steady-state power

750 W

Rated peak power

750 W

CAUTION:

This equipment is designed to permit the connection of the earthed conductor of the

DC supply circuit to the earthing conductor at the equipment.

If this connection is made, all of the following must be met:

This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply

system earthing electrode conductor is connected.

This equipment must be located in the same immediate area (such as adjacent cabinets) as any

other equipment that has a connection between the earthed conductor of the same DC supply
circuit and the earthing conductor, and also the point of earthing of the DC system. The DC

system must be earthed elsewhere.

The DC supply source is to be located within the same premises as the equipment.

Switching or disconnecting devices must not be in the earthed circuit conductor between the
DC source and the point of connection of the earthing electrode conductor.

CAUTION:

To reduce the risk of electric shock or energy hazards:

This equipment must be installed by trained service personnel, as defined by the NEC and IEC

60950-1, Second Edition, the standard for Safety of Information Technology Equipment.

Connect the equipment to a reliably grounded SELV source. An SELV source is a secondary
circuit that is designed so normal and single fault conditions do not cause the voltages to

exceed a safe level (60 V DC).

The branch circuit overcurrent protection must be rated 24 A.