Programming Reset-to-Preset Value

The Reset-to-Preset Value is programmed by entering the following:

A)

Unit must be in the “Program” mode.

B)

The Reset-to-Preset must first be enabled before you can store any values. To accomplish this,

depress . A zero (0) disables a

ENT

CIR# - 1 - 6

6

-

-

(0 or 1)

-

ENT

-

function and a one (1) enables it.

C)

Once the Reset-to-Preset has been enabled, you can store a value in memory. This is accom-

plished by depressing

ENT

CIR# - 1 - 6

0

-

-

(Desired Reset Value)

-

ENT

-

NOTE: Valid numbers for CIR# 160 are zero (0) through the programmed scale factor, less one (1).

.

3.14: Motion Detector

A programmable Motion Detect output will energize a relay when the transducer speed exceeds the

customer’s preprogrammed RPM value.

The motion detector is set by entering the following:

A)

Unit must be in the “Program” mode.

B)

The motion detect must first be enabled before you can store any values. To accomplish this,

depress . A one (1) will enable the motion

ENT

CIR# - 5 - 5 -

(0 or 1)

-

ENT

-

detect output circuit, and LS6 will now be your motion detect output relay. If a zero (0) is

entered, the motion detect feature is disabled and LS6 will function as a normal limit switch.

C)

To set the value at which the motion detect relay energizes, depress

ENT

CIR# - 1 - 7

6

-

-

(RPM Value)

-

ENT

-

NOTE: A CIR #176 can only be entered if the motion detect option is enabled.

.