Chapter 3: programming, Security input, Initialization – AMETEK 1995A Micro-Set PLS User Manual

Page 9: Scale factor

Advertising
background image

5

Installation and Maintenance Manual

Chapter 3: Programming

Chapter 3: Programming

3.1: Security Input

The security input is often referred to as the “Run/Program” input. This input is located on the 16-place

terminal strip and is discussed in Chapter 4: Expansion Modules. This input prevents unauthorized

changes to the programmed functions. With the unit in the “Program” mode, all functions of the control-

ler can be programmed. With the unit in the “Run” mode, all setpoints, reset-to-preset, motion detect

and other operational functions can be verified, but the programmed information cannot be changed.

3.2: Initialization

The following key commands should be entered on the

keypad to clear all programmed data upon installation and PRIOR to programming. This sequence

clears all programmed data. All operating parameters must be reprogrammed after using this initializa-

tion function.

3.3: Scale Factor

NOTE: Programming of the desired scale factor or the number of outputs will delete all programmed

data held in memory. Therefore, these should be the first steps in your setup procedure.

The 1995A is available with two scale factors: 360 or 1,000.

To program the scale factor, the following procedures must be followed:

1) Unit must be in the “Program” mode.

2) Depress

-or-

NOTE: ON UNITS WITH SOFTWARE OPTION “P”, THE SCALE FACTOR IS

PERMANENTLY SET AT 360.

ENT

CIR# - 9 - 9

5

-

-

ENT

CIR# - 3 - 6

0

-

-

ENT

CIR# - 9 - 9

9

-

-