PREPARING THE POLY PANELS AND H-CHANNELS:
1. The ribs of the double wall poly panels are oriented in a vertical direction. For each cabinet

height, cut the vertical dimension of the panels to be equal to the cabinet to ceiling distance
less approximately

6”. Cut using a sharp knife and a straight edge. For best results, use

specialized cutting tools like the Guardian Knife Guide and Coro-

Claw™ by Saw Trax Mfg.

Inc., to cut across or with the ribs respectively.

2. After cutting, remove protective film from both sides of the plastic panel.
3. Plastic H-channels are used to join adjacent poly panels that are not connected with the

lateral brace accessory. The H-channels should be cut to the cabinet to ceiling distance
less approximately 13 inches. The plastic H-channels are saw cut.