9

ACCESS FLOOR
For access floor installations, a door standoff kit (PN 32870-X01 for the double door or PN
32870-X02 for the single right door) is required. The standoff moves the door assembly
away from the cabinet by 2.5” so that there is enough clearance for the floor mounting
hardware.

In an access floor installation, ensure that the floor is strong enough to support the weight of
the door (320 lbs for the double door and 280 lbs for the single door).

Drill four clearance holes (two for each side panel) for 3/8” bolts or threaded rod into the
floor tile using the floor drilling template to accurately locate the holes. The template is not
included with the door; it must be ordered separately, 32875-X01 for the double door or
32875-X02 for the single door.

Bracing to the subfloor
In an access floor installation, ensure that the floor is strong enough to support the fully
populated computer cabinets. Add subfloor bracing to provide the proper support for
equipment.

Fig. 2.2.1 Subfloor bracing

Advertising