Appendices, Appendix a: specifications, Table a.1: pm ipdu specifications – Avocent Cyclades PM IPDU User Manual

Page 47

Advertising
background image

37

Appendices

Appendix A: Specifications

Table A.1: PM IPDU Specifications

Unit

Input
Voltage

Max Output
Current

Max Output
Each Outlet

Operating
Temp

Weight

Width

Depth

Height

PM10-15A

100-125 VAC 15A (12A)

15A (12A)

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10-20A,
PM10-L20A

100-125 VAC 20A (16A)

15A (12A)

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10-L30A

100-125 VAC 30A (24A)

15A (12A)

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10i-10A

100-240 VAC 10A

10A

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10i-15A

100-240 VAC 15A (12A)

10A (8A)

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10i-16A

100-240 VAC 16A

10A

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10i-20A

100-240 VAC 20A (16A)

10A (8A)

10-50 ºC

3.64 kg

17 in

8 in

1.75 in

PM10i-32A,
PM10i-32Au

100-240 VAC 32A

10A

0-50 ºC

5.45 kg

17 in

11.5 in

1.75 in

PM10i-L30A

100-240 VAC 30A (24A)

10A (8A)

0-50 ºC

5.45 kg

17 in

11.5 in

1.75 in

PM20-20A,
PM20-L20A

100-125 VAC 20A (16A)

15A (12A)

10-50 ºC

7.73 kg

1.8 in

2.2 in

66 in

PM20-L30A

100-125 VAC 30A (24A)

15A (12A)

10-50 ºC

7.73 kg

1.8 in

2.2 in

66 in

PM20i-16A

100-240 VAC 16A

10A

0-50 ºC

7.73 kg

2 in

2.8 in

66 in

PM20i-20A,
PM20i-L20A

100-240 VAC 20A (16A)

10A (8A)

0-50 ºC

7.73 kg

2 in

2.8 in

66 in

PM20i-L30A

100-240 VAC 30A (24A)

10A (8A)

0-50 ºC

7.73 kg

2 in

2.8 in

66 in

PM20i-32A

100-240 VAC 32A

10A

10-50 ºC

7.73 kg

2 in

2.8 in

66 in

A P P E N D I C E S