44 Cyclades PM IPDU Installer/Administrator/User Guide

Figure C.1: PM10-L30A IPDU Circuit Breakers

PM10i-L30A IPDU

The PM10i-L30A IPDU has two 15-amp circuit breakers. The first circuit breaker controls outlets 6
through 10; the second controls outlets 1 through 5. In the event that the total current flow to outlets
6 through 10 exceeds 15 amps due to equipment connected to these outlets, the first circuit breaker
will trip causing outlets 6 through 10 to shutdown. This does not affect outlets 1 through 5, which
are controlled by the second circuit breaker.

The PM IPDU controller is installed so that tripping either or both breakers will not render
it inoperative.

When either circuit breaker trips, only the power outlets of that segment will be affected, and half
of the outlets remain operative.