Signals for the ep applicator, Als 230, Operators manual – Avery ALS 230 User Manual

Page 60: 3 signals for the ep applicator

Advertising
background image

Operators Manual

ALS 230

Release 11/05

Page 58

Connections and signals

8.2.3

Signals for the EP applicator

For controlling the applicator the signals air stream, cylinder valve and blow on are necessary.
After a product signal has occurred the labelling cylinder valve is switched active after the delay
STAD. However if at this time the applicator is not in the home position then error message
E__2 is generated. After the delay time APT1 the blow on valve is switched active for the time
APT2.
When APT2 is completed both the labelling cylinder valve and the blow on valve signals are
switched inactive. If the control does not read the home position in the time given - 3* (APT1+
APT2) - than the error message E__2 is generated.

Productstart

Cylinder valve

Dispense label
+ Airstream valve

Blowon valve

Homeswitch

1

2

Missing Label: Labeller not ready for dispense

Error: Applicator not in homeposition

3

Error: Homeposition not detected

STAD

APT1

APT3

APT2

1

3

STAD

STAD

APT1

4 * (APT1 + APT2)

STAD

2

Figure 12 Timing EP applicator