Installation, Operation & Maintenance

HKV SERIES

Heat Controller, LLC

10

Installation of Supply and Return Piping
Follow these piping guidelines.

1. Install a drain valve at the base of each supply and return

ULVHUWRIDFLOLWDWHV\VWHPÀXVKLQJ

2. Install shut-off / balancing valves and unions at each unit

to permit unit removal for servicing.

3. Place strainers at the inlet of each system

circulating pump.

4. Select the proper hose length to allow slack between

FRQQHFWLRQSRLQWV+RVHVPD\YDU\LQOHQJWKE\WR
XQGHUSUHVVXUH

5. Refer to Table 1. Do not exceed the minimum bend radius

for the hose selected. Exceeding the minimum bend
radius may cause the hose to collapse which reduces
ZDWHUÀRZUDWH,QVWDOODQDQJOHDGDSWHUWRDYRLGVKDUS
bends in the hose when the radius falls below the
required minimum.

Insulation is not required on loop water piping except where
the piping runs through unheated areas or outside the building
or when the loop water temperature is below the minimum
expected dew point of the pipe ambient. Insulation is
required if loop water temperature drops below the dew
point.

3LSHMRLQWFRPSRXQGLVQRWQHFHVVDU\ZKHQ7HÀRQWKUHDGHG
WDSHLVSUHDSSOLHGWRKRVHDVVHPEOLHVRUZKHQÀDUHGHQG
connections are used. If pipe joint compound is preferred, use
compound only in small amounts on the male pipe threads of
WKH¿WWLQJDGDSWHUV3UHYHQWVHDODQWIURPUHDFKLQJWKHÀDUHG
surfaces of the joint.

Table 1: Metal Hose Minimum Bend Radii

Figure 3: Supply/Return Hose Kit

Piping Installation

Note: When anti-freeze is used in the loop, assure that
LWLVFRPSDWLEOHZLWK7HÀRQWDSHRUSLSHMRLQWFRPSRXQG
employed.

0D[LPXPDOORZDEOHWRUTXHIRUEUDVV¿WWLQJVLVIRRWSRXQGV
>1P@,IDWRUTXHZUHQFKLVQRWDYDLODEOHWLJKWHQ¿QJHUWLJKW
SOXVRQHTXDUWHUWXUQ7LJKWHQVWHHO¿WWLQJVDVQHFHVVDU\

2SWLRQDOSUHVVXUHUDWHGKRVHDVVHPEOLHVGHVLJQHGVSHFL¿FDOO\
for use with Heat Controller, Inc., units are available. Similar
hoses can be obtained from alternate suppliers. Supply and
UHWXUQKRVHVDUH¿WWHGZLWKVZLYHOMRLQW¿WWLQJVDWRQHHQGWR
prevent kinking during installation.

Refer to Figure 3 for an illustration of a Supply/Return Hose Kit.
External Pipe Thread (EPT) adapters secure hose assemblies
to the unit and risers. Install hose assemblies properly and
check them regularly to avoid system failure and reduced
service life.

Rib Crimped

Length

(2 ft [0.6m] Length Standard)

Swivel
Brass
Fitting

Brass

Fitting

EPT

CAUTION! Piping must comply with all applicable codes.

Hoses in Inches

Minimum Bend Radius

1” [25.4mm]

5.5” [140mm]

1.25” [31.8mm]

7.0” [178mm]

1.5” [38.1mm]

8.5” [216mm]

CAUTION! Corrosive system water requires corrosion
UHVLVWDQW¿WWLQJVDQGKRVHVDQGSRVVLEO\ZDWHUWUHDWPHQW

WARNING! Do not bend or kink supply lines or hoses.

CAUTION!

!

!

WARNING!

!

!

CAUTION!

!

!