Blower performance, Hkv 150 blower performance, Table continued from previous page – Comfort-Aire HKV300A User Manual

Page 33: Hkv series, Installation, operation & maintenance, Heat controller, llc

Advertising
background image

Installation, Operation & Maintenance

HKV SERIES

Heat Controller, LLC

32

Blower Performance

HKV 150 Blower Performance

5400

Turns Open

4

3.5

5.5

5

4.5

3.5

3

2.5

1.5

1

6

6

5

4.5

4

3.5

5500

BHP

2.04

2.14

2.24

2.34

2.44

2.54

2.64

2.74

2.84

3.09

3.14

3.24

3.34

3.44

3.54

3.69

5500

Sheave/Mtr

B

A

A

A

A

A

A

A

A

D

E

E

E

E

E

E

5500

RPM

704

729

756

783

810

836

859

883

907

929

952

972

993

1014

1035

1055

5500

Turns Open

4

6

5.5

4.5

4

3.5

3

2

1.5

1

6

5.5

5

4.5

4

3.5

5600

BHP

2.14

2.24

2.34

2.44

2.54

2.64

2.74

2.84

3.00

3.14

3.24

3.34

3.44

3.54

3.69

3.79

5600

Sheave/Mtr

B

A

A

A

A

A

A

A

D

D

E

E

E

E

E

E

5600

RPM

714

740

767

794

818

844

868

892

916

938

959

981

1002

1023

1043

1063

5600

Turns Open

3.5

6

5

4.5

4

3

2.5

2

1.5

1

6

5.5

4.5

4

3.5

3

5700

BHP

2.24

2.34

2.44

2.54

2.64

2.74

2.89

3.04

3.14

3.24

3.34

3.44

3.59

3.74

3.84

3.94

5700

Sheave/Mtr

B

A

A

A

A

A

A

D

D

E

E

E

E

E

E

E

5700

RPM

726

752

779

803

829

854

878

902

925

948

970

990

1011

1031

1051

1071

5700

Turns Open

3

5.5

5

4

3.5

3

2

2

1

6

5.5

5

4.5

4

3.5

3

5800

BHP

2.34

2.44

2.54

2.64

2.74

2.84

3.00

3.14

3.24

3.34

3.44

3.59

3.74

3.84

3.94

4.04

5800

Sheave/Mtr

A

A

A

A

A

A

D

D

D

E

E

E

E

E

E

E

5800

RPM

738

763

788

813

839

864

888

911

934

955

977

998

1019

1039

1058

1077

5800

Turns Open

6

5

4.5

4

3.5

2.5

2

1.5

1

6

5.5

5

4.5

4

3.5

2.5

5900

BHP

2.44

2.54

2.64

2.74

2.89

3.04

3.14

3.24

3.34

3.49

3.64

3.74

3.84

3.94

4.09

4.19

5900

Sheave/Mtr

A

A

A

A

A

D

D

D

E

E

E

E

E

E

E

E

5900

RPM

750

775

799

824

849

874

898

921

944

964

986

1007

1027

1046

1068

1086

5900

Turns Open

5.5

5

4

3.5

3

2.5

2

1.5

6

5.5

5

4.5

4

3.5

3

2.5

6000

BHP

2.54

2.64

2.74

2.89

3.04

3.14

3.24

3.34

3.49

3.64

3.74

3.84

3.99

4.14

4.24

4.34

6000

Sheave/Mtr

A

A

A

A

D

D

D

D

E

E

E

E

E

E

E

E

6000

RPM

758

783

808

833

858

880

904

927

950

972

993

1014

1033

1053

1073

1092

6000

Turns Open

5.5

4.5

4

3.5

3

2.5

1.5

1

6

5.5

5

4.5

4

3.5

3

2.5

6100

BHP

2.64

2.74

2.89

3.04

3.14

3.24

3.34

3.49

3.64

3.74

3.84

3.99

4.14

1.24

4.34

4.49

6100

Sheave/Mtr

A

A

A

D

D

D

D

D

E

E

E

E

E

E

E

E

6100

RPM

769

794

819

843

866

890

913

936

958

980

1000

1021

1041

1061

1081

1099

6100

Turns Open

5

4.5

3.5

3.5

2.5

2

1.5

1

6

5.5

4.5

4

3.5

3

2.5

2

6200

BHP

2.84

2.94

3.04

3.14

3.24

3.39

3.54

3.64

3.74

3.89

4.04

4.14

4.24

4.39

4.54

4.64

6200

Sheave/Mtr

A

A

D

D

D

D

D

E

E

E

E

E

E

E

E

E

6200

RPM

781

815

830

854

878

900

923

946

968

988

1009

1030

1050

1070

1089

1107

6200

Turns Open

4.5

4

3.5

3

2.5

2

1

6

5.5

5

4.5

4

3.5

3

2.5

2

6300

BHP

2.94

3.04

3.14

3.29

3.44

3.54

3.64

3.79

3.94

4.04

4.14

4.29

4.44

4.54

4.69

4.84

6300

Sheave/Mtr

A

D

D

D

D

D

D

E

E

E

E

E

E

E

E

E

6300

RPM

793

817

841

863

886

910

933

955

977

997

1018

1038

1058

1078

1097

1115

6300

Turns Open

4.5

4

3.5

3

2

1.5

6

5.5

5

4.5

4

3

2.5

2

1.5

A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

Table Continued from Previous Page

All Data is Wet Coil

Airflow

(SCFM)

ESP

Airflow (cfm) at External Static Pressure (in. wg)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.10

1.20

1.30

1.40

1.50

Advertising