Unit commissioning & operating conditions, Hkv series, Installation, operation & maintenance – Comfort-Aire HKV300A User Manual

Page 41: Heat controller, llc

Advertising
background image

Installation, Operation & Maintenance

HKV SERIES

Heat Controller, LLC

40

Unit Commissioning & Operating Conditions

BUILDING COMMISSIONING

ALL HKV MODELS

Cooling °F [°C]

Heating °F [°C]

AMBIENT MIN - MAX DB

45-110 [7-43]

40-85 [4.5-29]

RETURN AIR MIN DB/WB

50/45 [10/7]

40 [4.5]

RETURN AIR MAX DB/WB

110/83 [43/28]

85 [29]

STANDARD UNIT ENTERING

WATER MIN* - MAX

40-120 [4.5-49]

60-90 [16-43]

EXTENDED RANGE UNIT** EN-

TERING WATER MIN* - MAX

30-120 [-1-49]

20-90 [-6.7-43]

*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumperclipped.

UNIT OPERATING LIMITS

All HKV Models

Cooling °F [°C]

Heating °F [°C]

AMBIENT MIN - MAX DB

50-100 [10-38]

50-85 [10-29]

RETURN AIR MIN DB/WB

65/60 [18/15.5]

60 [16]

RETURN AIR MAX DB/WB

95/75 [35/24]

80 [27]

STANDARD UNIT ENTERING

WATER MIN* - MAX

50-120 [10-49]

60-90 [16-43]

EXTENDED RANGE UNIT** EN-

TERING WATER MIN* - MAX

30-120 [-1-49]

20-90 [-6.7-43]

*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumper clipped.

Table 6: Building Commissioning

Table 6A: Unit Operating Limits

Environment – This unit is designed for indoor installation only.
Do not install in an area subject to freezing or where humidity
levels can cause cabinet condensation.
Power Supply±$YROWDJHYDULDWLRQRIRIQDPHSODWH
utilization voltage is acceptable.

Operation and performance is primarily dependent upon return
DLUWHPSHUDWXUHDLUÀRZZDWHUWHPSHUDWXUHZDWHUÀRZUDWHDQG
ambient air temperature. This water to air heat pump is capable
RIRSHUDWLQJRYHUDZLGHWHPSHUDWXUHUDQJHDQGZLWKÀRZUDWHV
of between 1.5 GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however
usually no more than one of these factors may be at a minimum
or maximum level at a time.

The commissioning table indicates air and water temperatures
which are suitable for initial unit commissioning in an environment
ZKHUHWKHÀRZUDWHDQGZDWHUWHPSHUDWXUHLVQRW\HWVWDEOHDQG
to avoid nuisance shut down of the units freeze and refrigerant
pressure safeties.

The operating table indicates the maximum and minimum
ranges of the unit.

)RUPRUHVSHFL¿FXQLWSHUIRUPDQFHUHIHUHQFHWKHSURGXFWFDWDORJ
the submittal data sheets or contact your supplier for assistance.