HKV 168 Blower Performance

All Data is Wet Coil

Airflow

(SCFM)

ESP

Airflow (cfm) at External Static Pressure (in. wg)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.10

1.20

1.30

1.40

1.50

4200

BHP

0.58

0.68

0.74

0.82

0.88

0.98

1.08

1.18

1.28

1.38

1.48

1.58

1.68

4200

Sheave/Mtr

B

B

B

B

A

A

A

A

A

A

A

A

C

4200

RPM

457

499

537

577

612

647

678

710

737

764

791

815

838

4200

Turns Open

6

5

3.5

2.5

6

5.5

4.5

3.5

3

2

1.5

1

3

4400

BHP

0.63

0.68

0.78

0.88

0.98

1.08

1.18

1.28

1.38

1.48

1.58

1.68

1.8

4400

Sheave/Mtr

B

B

B

B

A

A

A

A

A

A

A

C

C

4400

RPM

467

507

548

584

621

653

684

716

743

772

797

821

847

4400

Turns Open

5.5

4.5

3.5

2.5

6

5

4

3.5

2.5

2

1

3.5

3

4600

BHP

0.68

0.78

0.88

0.98

1.08

1.18

1.28

1.38

1.48

1.58

1.68

1.78

1.88

4600

Sheave/Mtr

B

B

B

B

A

A

A

A

A

A

A

C

C

4600

RPM

476

518

555

590

627

659

692

721

751

777

803

829

853

4600

Turns Open

5.5

4.5

3

2

5.5

5

4

3

2.5

1.5

1

3.5

2.5

4800

BHP

0.68

0.78

0.88

0.98

1.08

1.18

1.28

1.38

1.48

1.58

1.68

1.78

1.88

1.98

4800

Sheave/Mtr

B

B

B

B

B

A

A

A

A

A

A

C

C

C

4800

RPM

446

485

527

563

600

633

665

697

726

756

783

811

835

858

4800

Turns Open

6

5

4

3

1.5

5.5

4.5

4

3

2.5

1.5

4

3

2.5

5000

BHP

0.68

0.78

0.88

0.98

1.08

1.18

1.28

1.48

1.58

1.68

1.78

1.88

1.98

2.08

5000

Sheave/Mtr

B

B

B

B

B

A

A

A

A

A

A

C

C

E

5000

RPM

452

495

532

567

604

636

670

700

729

759

786

813

838

864

5000

Turns Open

6

5

4

2.5

1.5

5.5

4.5

3.5

3

2

1.5

4

3

2.5

5200

BHP

0.86

0.96

1.06

1.16

1.26

1.36

1.46

1.56

1.66

1.76

1.86

2.06

2.16

2.26

5200

Sheave/Mtr

B

B

B

B

A

A

A

A

A

A

A

E

E

E

5200

RPM

460

500

536

570

606

638

671

701

729

759

786

814

839

865

5200

Turns Open

6

4.5

3.5

2.5

6

5.5

4.5

3.5

2.5

2

1

4

3.5

2.5

5400

BHP

0.86

0.96

1.06

1.18

1.28

1.38

1.48

1.58

1.68

1.78

1.88

2.08

2.18

2.28

5400

Sheave/Mtr

B

B

B

B

A

A

A

A

A

A

A

E

E

E

5400

RPM

463

504

539

576

609

641

674

703

734

762

788

816

841

867

5400

Turns Open

5.5

4.5

3.5

2.5

6

5

4.5

3.5

2.5

2

1

4

3.5

2.5

5600

BHP

0.88

0.98

1.08

1.28

1.38

1.48

1.58

1.68

1.78

1.88

2.08

2.18

2.24

2.44

5600

Sheave/Mtr

B

B

B

B

A

A

A

A

A

A

D

E

E

E

5600

RPM

474

510

545

581

613

647

677

706

737

764

793

818

843

869

5600

Turns Open

5.5

4

3

2

6

5

4

3

2.5

1.5

1.5

4

3.5

2.5

5800

BHP

0.88

0.98

1.08

1.18

1.28

1.48

1.58

1.68

1.78

1.88

2.08

2.18

2.28

2.38

2.48

5800

Sheave/Mtr

B

B

B

B

B

A

A

A

A

A

D

D

E

E

E

5800

RPM

440

481

517

551

586

618

651

681

710

740

767

795

821

845

872

5800

Turns Open

6

5

4

3

2

5.5

4.5

4

3

2

2

1.5

3.5

3

2

6000

BHP

0.98

1.08

1.18

1.28

1.38

1.48

1.68

1.78

1.88

2.08

2.18

2.28

2.38

2.48

2.58

6000

Sheave/Mtr

B

B

B

B

B

A

A

A

A

D

D

D

E

E

E

6000

RPM

455

492

526

563

595

628

658

687

718

745

774

800

826

852

876

6000

Turns Open

6

5

3.5

2.5

1.5

5.5

4.5

3.5

3

2.5

2

1.5

3.5

3

2

6200

BHP

1.06

1.18

1.28

1.38

1.48

1.68

1.78

1.88

1.98

2.08

2.28

2.38

2.48

2.68

2.78

6200

Sheave/Mtr

B

B

B

B

B

A

A

A

A

D

D

D

E

E

E

6200

RPM

459

499

533

569

600

633

663

691

722

749

777

803

828

854

878

6200

Turns Open

5.5

4.5

3.5

2.5

1.5

5.5

4

3.5

2.5

2.5

2

1

3.5

3

2

6400

BHP

0.98

1.08

1.28

1.38

1.48

1.68

1.78

1.88

1.98

2.08

2.28

2.38

2.48

2.68

2.78

2.88

6400

Sheave/Mtr

B

B

B

B

B

A

A

A

A

D

D

D

D

E

E

E

6400

RPM

441

478

513

549

581

614

644

672

703

730

759

785

810

837

861

887

6400

Turns Open

6

5.5

4

3

2

6

5

4

3.5

3

2.5

1.5

1

3

2.5

2

6600

BHP

1.08

1.28

1.38

1.48

1.66

1.78

1.88

1.98

2.08

2.28

2.46

2.58

2.68

2.88

2.98

6600

Sheave/Mtr

B

B

B

B

B

A

A

A

D

D

D

D

E

E

E

6600

RPM

456

495

529

561

595

625

656

685

712

741

767

795

820

844

870

6600

Turns Open

6

5

3.5

2.5

2

5.5

4.5

4

3.5

3

2

1.5

3.5

3

2.5

6800

BHP

1.26

1.38

1.48

1.58

1.68

1.88

1.98

2.08

2.28

2.38

2.48

2.68

2.88

2.98

6800

Sheave/Mtr

B

B

B

B

A

A

A

D

D

D

D

D

E

E

6800

RPM

471

506

539

574

604

633

664

692

721

747

773

800

825

851

6800

Turns Open

5.5

4.5

3.5

2.5

6

5.5

4.5

4

3

2.5

2

1

3.5

2.5

7000

BHP

1.28

1.48

1.58

1.68

1.88

1.98

2.08

2.28

2.46

2.58

2.68

2.88

2.98

7000

Sheave/Mtr

B

B

B

B

A

A

D

D

D

D

D

D

E

7000

RPM

486

520

555

586

615

647

674

704

730

756

784

808

835

7000

Turns Open

5

4

3

2

6

5

4.5

3.5

3

2.5

1.5

1

3

A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.