* 0.5 MH is a typical starting point for the Common Mode Line Filters. By increasing or decreasing the value of L

you can set the drain current to a minimum to meet your requirements.

Driver to Motor Cable AWG Table

1 Amp (Peak)

5 Amp (Peak)

Length (Feet) 10 25 50 75

100 Length (Feet) 10 25 50 75

100

Minimum

AWG

20 20 18 18

16

Minimum

AWG

16 16 14 12

12

2 Amp (Peak)

6 Amp (Peak)

Length (Feet) 10 25 50 75

100 Length (Feet) 10 25 50 75

100

Minimum

AWG

20 18 16 14

14

Minimum

AWG

14 14 14 12

12

3 Amp (Peak)

7 Amp (Peak)

Length (Feet) 10 25 50 75

100 Length (Feet) 10 25 50 75

100

Minimum

AWG

18 16 14 12

12

Minimum

AWG

12 12 12 12

12

4 Amp (Peak)

Length (Feet) 10 25 50 75

100

Minimum

AWG

18 16 14 12

12

Driver to Motor Supply Cable Wire Size

NOTE: These recommendations will provide optimal protection against EMI and RFI. The actual cable type, wire

gauge, shield type and filtering devices used are dependent on the customer’s application and system.

NOTE: Always use Shielded/Twisted Pairs for the Driver DC Supply Cable, the AC Supply Cable and the Driver to

Motor Cable.