4 power buses, Power buses, Figure 3. circuit breaker panel block diagram – ADC PowerWorx Circuit Breaker Panel With Reset Switch User Manual

Page 10

Advertising
background image

ADCP-80-570 • Issue 2 • March 2006

Page 4
© 2006, ADC Telecommunications, Inc.

• Rear protective input terminal covers (2) and output/alarm terminal cover (1)Used to

prevent accidental contact with the alarm and power terminals.

• #6-32 Screws (4)Used to fasten output/alarm terminal cover to rear of panel chassis.

• Designation card and card holder (1)Used to record information about the protected

equipment. Cards and clear cover insert into the card holder.

• Voltage label (1)Used to indicate whether the input voltage is –48 or –24 Vdc.

1.4

Power Buses

Each circuit breaker panel has two isolated power buses. Each bus distributes the input power to
the output power circuits. In each bus circuit, current flows from the input power bus, through
the circuit breaker, to the output power circuit. The current capacity of each bus is 45 Amps
maximum.

Figure 3

is a block diagram of the power buses.

Figure 3. Circuit Breaker Panel Block Diagram

1
2
3
4
5
6
7

BATTERY

RETURN

BATTERY A

RETURN A

POWER A LED

BREAKER
ALARM A LED

1
2
3
4
5
6
7

BATTERY

RETURN

BATTERY B

RETURN B

BUS A

RETURN A

POWER B LED

ALARM RESET PUSHBUTTON

BREAKER ALARM B LED

BUS B

RETURN B

–24V/–48V

–24V/–48V

C

NO

NC

C

NO

NC

SYSTEM ALARM

CONNECTIONS

20691-A

FA

FB