ADCP-80-570 • Issue 2 • March 2006

Page 14
© 2006, ADC Telecommunications, Inc.

Test 1: Input Battery to Input Return—Use the following procedure:

1. Connect one test probe to the A bus BATT input power terminal and the other test probe to

the A bus RTN input power terminal (

Figure 7

).

Figure 7. Test 1: Input Battery to Input Return

2. Verify that no continuity exists between the BATT input and RTN input terminals.

3. Repeat the test procedure for the B bus.

Test 2: Input Battery to Output Battery—Use the following procedure (

Figure 8

):

1. Starting on the A bus, at the output terminal for circuit 1, connect the negative test probe to

the bus A input BATT power terminal and the positive test probe to bus A output BATT
power terminal for the circuit being tested.

Figure 8. Test 2: Input Battery to Output Battery

2. Turn on circuit breaker A1.

3. Verify that continuity exists between the specified terminals.

4. Repeat the test procedure for each remaining circuit (A 2-7, B 1-7).

20635-A

TEST 1- POWER BUS A:

VERIFY NO CONTINUITY
EXISTS BETWEEN BATT

AND RTN TERMINALS

TEST 1- POWER BUS B:

VERIFY NO CONTINUITY
EXISTS BETWEEN BATT

AND RTN TERMINALS

20636-A

TEST 2- POWER BUS B:

VERIFY CONTINUITY EXISTS

BETWEEN INPUT AND

OUTPUT BATT TERMINALS

TEST 2- POWER BUS A:

VERIFY CONTINUITY EXISTS

BETWEEN INPUT AND

OUTPUT BATT TERMINALS