Use the following procedure to install the circuit breaker panel in the rack:

1. Select either the 19-inch or 23-inch brackets.

2. Attach the mounting brackets to the sides of the chassis using the eight 5/16-inch (7.94

mm) 8-32 flathead thread-forming screws provided. Tighten the screws to 15 pound-force
inches (1.7 Newton meters) of torque to insure grounding. Refer to

Figure 12

.

Figure 12. Repositioning the Mounting Brackets (Optional)

3. Place the circuit breaker panel in the specified mounting space within the rack as shown in

Figure 13

.

4. Secure the panel to the rack using the four 3/8-inch (9.525 mm) long, 12-24 pan-head

screws and #12 flat washers provided (use star washers when required by local practice).
Tighten the screws to 27 pound-force inches (3.1 Newton meters) of torque.

Caution: When attaching the mounting brackets to the circuit breaker panel, use only the
5/16-inch (7.935 mm) long, chromate finish, flathead, thread forming screws supplied with the
panel. Use of any other hardware could cause contact with internal parts of the circuit breaker
panel. If parts are missing, please contact ADC.

Note: Provide one rack unit of space above and below the circuit breaker panel for air
circulation.

20638-A

ORIENTATION FOR

19-INCH RACK

NSTALLATION

ORIENTATION FOR

23-INCH RACK

INSTALLATION

5/16-INCH (7.94 MM)

8-32 FLAT-HEAD

THREAD-FORMING

SCREWS

TIGHTEN MOUNTING SCREWS

TO 15 POUND-FORCE INCHES

(1.7 NEWTON METERS) OF TORQUE