22 specifications – ADC PowerWorx Circuit Breaker Panel With Reset Switch User Manual

Page 16

Advertising
background image

ADCP-80-570 • Issue 2 • March 2006

Page 10
© 2006, ADC Telecommunications, Inc.

1.22 Specifications

Table 2

lists specifications for the circuit breaker panel.

Table 2. Circuit Breaker Panel Specifications

PARAMETER

SPECIFICATION

REMARKS

Physical

Weight

12 pounds (5.45 kilograms)

Dimensions (HxWxD)

1.75 x 17.13 x 11.0 inches
(44 x 435 x 280 mm)

See

Figure 6

.

Color

Putty white

Rack mounting

19- or 23-inch (EIA or
WECO hole spacing)

Flush or with a recess of 1, 2,
3, or 4 inches (25.4, 50.8,
76.2, or 101.6 mm)

Electrical

Operating voltages

–24 Vdc nominal

Input range: –21 to –30 Vdc

–48 Vdc nominal

Input range: –42 to –56 Vdc

Input current

45 Amps max. per bus

90 Amps max. per panel

Circuit breaker rating

5 or 10 Amps

Positions are labeled

Circuit breaker positions

7 per bus

14 per panel

Max. circuit breaker size

10 Amps rating

45 Amps per bus

Input terminal type

2-hole compression lug

Stud type accepting up to #6
AWG wire

Output terminal type

7-position screw-down barrier
terminal strip

Accepting a variety of wire
up to 12 AWG wire

Alarm contact current

1 Amp max.

Grounding connection

Two #10 studs and nuts on
0.625 centers

Environmental

Operating temperature

–5º C to +55º C

Storage temperature

–45º C to +85º C

Humidity range

0% to 95% humidity

No condensation

Altitude range

–197 feet (0.06 km) to 13,000
feet (3.96 km) above sea level

Acoustic noise

0 dBA above ambient

Heat dissipation (no load)

1 Watt per bus

Heat dissipation (fully loaded)

30 Watts max. at

25º C ambient

temperature, full load

Advertising