12 installing protective covers, Section 4.12 – ADC PowerWorx Circuit Breaker Panel With Reset Switch User Manual

Page 29

Advertising
background image

ADCP-80-570 • Issue 2 • March 2006

Page 23

© 2006, ADC Telecommunications, Inc.

6. Use a heat gun to apply heat to the heat shrink insulation until it tightens around the wire

and barrel end of the terminal.

7. Use the nuts (with captive washers) provided to secure the input power wires to the

specified terminals.

8. Connect the negative inputs to the negative (BATT) terminals on the A and B input power

terminal blocks.

9. Connect the positive inputs to the positive (RTN) terminals on the A and B input power

terminal blocks.

10. Use a torque wrench (with a 7/16-inch socket) to tighten the input power terminal block

nuts to 32 pound-force inches (3.6 Newton meters) maximum of torque.

11. Route the free ends of the input power cables to the office battery source.

12. Connect the input power cables to the office battery power source in accordance with

applicable local electrical codes and/or National Electrical Codes. Refer to

Appendix A

.

Do not apply power to the circuit breaker panel until instructed to do so for testing (see

Section 5

).

4.12 Installing Protective Covers

1. Snap the two small protective covers on the input and output terminals (

Figure 18

).

2. Fasten the large cover to the four corners of the output power terminal blocks using the

four #6-32 screws provided.

Figure 18. Installing Protective Covers

20644-A

COVER FOR

OUTPUT POWER

TERMINALS

COVER FOR

INPUT POWER

TERMINALS

COVER FOR

INPUT POWER

TERMINALS

Advertising