3-2 Receiving & Installation

MN2417

Several other factors should be carefully evaluated when selecting a location for installation:

1.

For effective cooling and maintenance, the system should be mounted on a flat,

smooth, noncombustible level surface. A concrete pad is ideal and provides a secure

installation.

2.

Installation should prevent water levels from reaching the generator. Drainage must be

adequate to keep concrete pad free from standing water.

3.

Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If

these items pose a problem, consider building a small fence or other break to protect

the unit from accumulation of debris.

4.

Installation should place the generator as close as possible to the transfer switch.

5.

At least forty--eight (48) inches clearance must be provided on all sides for air flow.

6.

Access must be provided to allow the enclosure covers to be opened or removed for

service and maintenance.

7.

Maximum Ambient temperature is 122°F (50°C).

Figure 3-2 Generator Mounting (Skid)

B1

B

A

A2

A1

TS130/175 only

(4 Holes)

A2

A1

TS25/45/80 only

(3 Holes)

A1

A2

A2

TS250 only

(4 Holes)

A2

A1

A2

A1

TA0000C10

BA0236A00

BA0236A02

TS400 only

(6 Holes)

A1

48

Holes each side

21

24

27

10.85401--G10

Table 3-2 Mounting Dimensions

Generator

A

A1

A2

B

B1

TS25

74

8.12

23.81

38

36

TS35

74

8.38

28.56

38

36

TS45

84

8.38

28.56

38

36

TS60

84

8.38

28.56

38

36

TS80

84

8.38

28.56

38

36

TS130

118

16.57

26.57

42

40

TS175

130

16.57

26.57

48

46

TS250

159

18.00

40.00

54

52

TS400

195

12.00

See Figure 3-2

66

63

Secure the Generator (Skid Mount only)

Six mounting bolts (eight for TS130/175/250) in the base frame secure the generator to the

shipping pallet. Remove these bolts, lift the generator and remove the shipping pallet. Secure

the generator to the concrete pad using anchor hardware (not provided) in the base frame

mounting holes (holes are 0.66” diameter). See Figure 3-2 and Table 3-2. Anchor bolts must be

long enough to extend through the generator mounting frame.