3-4 Receiving & Installation

MN2417

Electrical Connections Class 1 wiring methods must be used for field wiring connections to terminals of a class 2

circuit. It is the responsibility of the owner/operator to arrange for these procedures to be

performed by a licensed electrical contractor and ensure conformance to all applicable codes

including local codes peculiar to your municipality/city/county and state. Wire size and insulation

type should be as required by NEC (National Electrical Code) and local codes.

Warning: Never connect this generator to the electrical system of any building unless a licensed

electrician has installed an approved transfer switch. The national electrical code (NEC)

requires that connection of a generator to any electrical circuit normally powered by means of

an electric utility must be connected by means of approved transfer switch equipment to

isolate the electrical circuit from the utility distribution system when the generator is

operating. Failure to isolate the electrical circuits by such means may result in injury or death

to utility power workers due to backfeed of electrical energy onto the utility lines.

Warning: Incorrect installation of this generator set could result in property damage, injury or death.

Connection of the generator to its fuel source must be done by a qualified professional

technician or contractor.

WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before

you ensure that grounds are connected. Electrical shock can cause serious or fatal injury. NEC

requires that the frame and exposed conductive surfaces (metal parts) be connected to an

approved earth ground. Local codes may also require proper grounding of generator systems.

Intended Use The intended purpose of this generator set is to provide electrical power when the main utility power

supply is interrupted. Therefore, it is important that all the wiring that connects the generator set with

your house, transfer switch, distribution box, battery charger, etc. be properly installed.

Protection

Single Phase circuit protection is provided within the generator. The power output connections

are rated and sized according to the KW of the generator. Proper lead wire from these points to

the automatic transfer switch (or load switching device) is mandatory. See transfer switch

information for corresponding generator input terminals.

Three phase circuit protection is provided by the generator. When connecting the generator

output to an electrical load, a UL listed circuit breaker with the appropriate ratings shall be

provided within 25 feet of the Genset. Use only copper wires.

Table 3-3 Standby Power Ratings

Generator

Electrical Load Capacity Standby Power Ratings

Generator

Catalog

1 Phase

3 Phase

Catalog

No.

kVA kW

Volts

Amps *

kVA

kW

Volts

Amps

TS25

18

18

240/120

75/2x75

25/25/25

20/20/20

208/240/480

69/60/30

TS35

25

25

240/120

104/2x104

37/37/37

30/30/30

208/240/480

104/90/45

TS45

27

27

240/120

112/x2112

46/46/48

37/37/38

208/240/480

128/111/57

TS60

43

43

240/120

179/2x179

60/60/61

48/48/49

208/240/480

166/144/73

TS80

45

45

240/120

187/2x187

72/72/81

58/58/65

208/240/480

201/174/97

TS130

70

70

240/120

291/2x291

131/131/134

105/105/107

208/240/480

364/315/160

TS175

100 100

240/120

416/2x416

169/169/175

135/135/140

208/240/480

468/405/210

TS250

175 175

240/120

729/2x729

250/250/250

200/200/200

208/240/480

693/601/300

TS400

250 250

240/120

1041/2x1041

400/400/400

320/320/320

208/240/480

1110/962/481

* Example 2x75 means 2 lines (Line to Neutral) of 120V @ 75 amps each.

Table 3-4 Prime Power Ratings

Generator

Electrical Load Capacity Prime Power Ratings

Generator

Catalog

1 Phase

3 Phase

Catalog

No.

kVA kW

Volts

Amps *

kVA

kW

Volts

Amps

TS25

18

18

240/120

75/2x75

23/23/23

18/18/18

208/240/480

62/54/27

TS35

22

22

240/120

91/2x91

33/33/33

27/27/27

208/240/480

93/81/40

TS45

25

25

240/120

104/2x104

44/44/44

35/35/35

208/240/480

121/105/52

TS60

40

40

240/120

166/2x166

56/56/56

45/45/45

208/240/480

156/135/67

TS80

43

43

240/120

179/2x179

69/69/75

55/55/60

208/240/480

190/165/90

TS130

66

66

240/120

275/2x275

119/119/121

95/95/97

208/240/480

329/285/145

TS175

95

95

240/120

395/2x395

156/156/159

125/125/127

208/240/480

433/375/190

TS250

160 160

240/120

666/2x666

227/227/227

180/180/180

208/240/480

624/541/270

TS400

240 240

240/120

1000/2x1000

365/365/365

292/292/292

208/240/480

1013/878/439

* Example 2x75 means 2 lines (Line to Neutral) of 75 amps each.